NetSure
™
DC/DC Converter Module
User Manual, UM1C48241500 (Revision E, July 20, 2015)
Spec. No: 1C48241500
Code: UM1C48241500
Model No: C48/24-1500
Revision E, July 20, 2015
1
Introduction
Overview
The C48/24-1500 is a compact DC/DC converter module which
offers efficient power conversion. It operates from a
nominal -48Vdc source to provide n24Vdc load power.
Specifications
DC Output Ratings
•
Voltage: N24 volts DC, negative ground.
Output voltage is adjustable from 24 to 28 volts DC via
the associated Controller.
•
Nameplate Rating: 24 to 28 Vdc, 1500W.
•
Regulation:
a.
Output Voltage Tolerance: < ±0.2% when the load is
50% and the temperature is from +15 to +35°C;
< ±0.5% when the load is 50% and the temperature is
from -5 to +55°C; < ±1% when the load is 50% and
the temperature is from -20 to +55°C.
b.
Temperature Regulation: < ±0.02% when the load is
50% at -48Vdc and temperature range is from -10°C
to +55°C.
c.
Dynamic Response: The dynamic response time at
rated input and output voltage is ≤ 200us and
overshot ≤ 5% for load changes at 50%-25%-50% and
50%-75%-50%.
d.
The output voltage is accurate at half load. At half
load, the error of output voltage is ≤ ±100mV. Static
regulation will give other voltage depending on load.
The default value at half load is 27V.
•
Filtering:
a.
Peak-peak voltage is ≤ 250mV at 1-100MHz and
normal output voltage.
b.
Psophemetic noise voltage is ≤ 2mV between
5-100% of the maximum load (output voltage
> 24V).
c.
Wideband noise is < 20mV rms between
25HZ-20kHz (test according to ETS300132).
d.
Output noise according to Telcordia GR-947-CORE:
< 38 dBrnC (between 5-100% of the maximum load,
output voltage > 24V).
•
Ripple Attenuation: Ripple attenuation is better than
+24dB, input to output and f < 360Hz.
DC Input Ratings
•
Voltage: Nominal -48 volts DC.
•
Nameplate Rating: -41 to -58.5 Vdc, 39.5A max.
•
Inrush Current: The peak value of the inrush current does
not exceed 2 times the maximum steady-state peak
value.
•
Input Regulation: ≤ ±0.1% when the load is 100% at -42
to -58.5 Vdc input and temperature is +25°C.
•
Temperature Coefficient: ≤ ±0.02%/°C over the specified
operating temperature range.
•
Typical Input Data: When equipped with one DC-DC
converter module.
a.
See
b.
Maximum Current: Input current is 39.5 amperes
at -41.0 volts DC input and full load.
Table 1.
Typical Input Data
Input
Voltage
Percent
of Full
Load
Input
Current
(Amps)
Efficiency
(%)
Typical Heat
Dissipation
(BTU/Hr)
42 VDC
0
0.125
--
18.02
25
9.388
95.661
58.28
50
18.803
95.416
122.84
75
28.714
94.217
235.77
100
38.888
92.835
394.06
48 VDC
0
0.122
--
20.02
25
8.218
95.516
60.33
50
16.431
95.336
125.12
75
25.055
94.181
237.34
100
33.887
92.800
396.04
58 VDC
0
0.105
--
20.93
25
6.811
95.286
63.55
50
13.601
95.141
130.57
75
20.713
94.049
243.05
100
27.987
92.689
402.69
Note:
The output voltage of the DC-DC converter module is initially
adjusted to 24 volts DC at 50% load and 48 volts DC input.
Environmental Ratings
•
Operation Temperature Range: -40°C to +80°C (-40°F to
+176°F), -20°C to +55°C (-4°F to +131°F) with full
performance.