EL-2MRS Emergency Lighting Unit
2/2
Emergi-Lite®
Tel: (888) 552-6467
Fax: (800) 316-4515
www.emergi-lite.com
10/16 750.1355 Rev. B
8. Restore power and press the test button (see figure 2). Lamp heads
will turn on.
Wall mount Conduit entry
1. Remove the top knockout on the top flange of the fixture (see figure 5).
2. Remove keyhole knockouts on the back plate and mount to the wall.
3. Secure conduit to knockout and feed wires into the fixture.
4. Make the proper connections (see figure 4):
a. For 120VAC, connect the black wire (120Vac) and white wire
(neutral) to the building utility.
b. For 277VAC, connect the orange wire (277Vac) and white wire
(neutral) to the building utility.
5. Connect the red wire to the battery positive terminal.
6. Snap top cover to back plate.
7. Restore power and press the test button (see figure 2). Lamp heads
will turn on.
Lamp adjustment
To adjust the lamps press down on the lamp head where it is marked
“open” and turn the head in the desired direction (see figure 6).
Relamping (see figure 7)
1. Using a flat head screwdriver, insert the blade into the slot between the
lamp cover and lamp body and then gently remove the lamp cover.
2. Install replacement lamps and snap lamp cover back into place.
Maintenance
None required. Replace the batteries as needed according to ambient
conditions. Equipment must be tested regularly in accordance with local
codes.
This unit comes with a (3) three year limited warranty.
CONDUIT (No
B
B
NSFORMER
CONNECTION)
K
NNECTION)
NECTOR
Wire connector
White (neutral)
Black (120 Vac)
Transformer
Housing
Conduit (not provided)
Back plate
Battery
Figure 5
Orange (277Vac)
Figure 6
Figure 7