background image

®

Emergi-Lite®

Tel: (888) 552-6467 

Fax: (800) 316-4515

www.emergi-lite.com

10/16 750.1355  Rev. B

1/2

EL-2MRS Emergency Lighting Unit

EL-2MRS Emergency Lighting Unit

Self-powered Halogen Light Unit

IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always 
be followed including the following:      

READ AND FOLLOW ALL SAFETY 
INSTRUCTIONS

1.

All servicing should be performed by qualified service personnel.

2.

All unused wires must be insulated to prevent shorting.

3.

Do not use outdoors.

4.

Do not let power supply cords touch hot surfaces.

5.

Do not mount near gas or electric heaters.

6.

Use caution when handling batteries. Battery acid can cause burns to the skin 
and eyes.  If acid is spilled on the skin or eyes, flush affected area with fresh 
water and contact a physician immediately. 

7.

Avoid possible shorting.

8.

Equipment should be mounted in locations and at heights where it will not 
readily be subjected to tampering by unauthorized personnel.

9.

The use of accessory equipment not recommended by the manufacturer may 
cause an unsafe condition.

10. Do not use this equipment for other than intended use.
11. When relamping, only use lamps specified in the fixture.
12. Allow battery to charge for 24 hours before first use.

SAVE THESE

 

INSTRUCTIONS  

Installation Instructions

 

 

1. Turn of AC power.

2. Using a flat head screwdriver, insert the blade into the slot and gently 

pry off the front cover (see figure 1).

Wall & Ceiling Mount    

1. Remove battery from back plate.

2. Remove the appropriate knockouts in the back plate to mount to a 

standard junction box.

3. Feed unit wires through the center hole of the back plate.

4. Make the proper connections (see figure 4): 

a.   For 120VAC, connect the black wire (120Vac) and white wire 

(neutral) to the building utility. 

b. For 277277VAC, connect the orange wire (277Vac) and white wire 

(neutral) to the building utility. 

c. Feed wires back into the junction box.

5. Mount and secure the back plate to the junction box.

6. Reattach the battery to the back plate and connect the battery ensuring 

the red wire is connected to the positive terminal.

7. Snap top cover to back plate.

IMPORTANT:

Install product no higher than the maximum 
mounting height of 10 feet from the floor.

WARNING:

Risk of Shock.  

Disconnect Power before Installation.

Figure 2

1.

Manual battery test switch

2.

Red LED (indicates normal operation)

Figure 1

BACK PLATE

SLOT

CREW(8#32*1”)

RANSFORMER

OUSING

WHITE(NEUT

JUNC

BLACK
(FOR 120VAC CO

LAMP ASSEMBLY

Figure 3

Wire 

Back plate

Center hole

Screw

Transformer

Housing

Lamp assembly

Black (120Vac)

Junction box

White (neutral)

connector

Orange (277Vac)

BLACK

WHITE

ORANGE

GREEN

G

R

W

277VAC    120VAC

INPUT       INPUT

WIRING

G

R

EEN GROUND

WHI

T

E

BL

ACK

Figure 4

ORA

N

G

E