EES-401 Series Ultrasonic Energy Meter
Revision: 3.0.1
Page 11 of 90
90 ~ 98
Diagnoses: Signal strength and signal quality (Window M90), TOM/TOS*100 (Window M91), flow
sound velocity (Window M92), total time and delta time (Window M93), Reynolds number and factor
(Window M94), etc.
+0 ~ -2 Appendix: power on/off time, total working hours, on/off times and a single-accuracy function
calculator.
Attention
The other windows for hardware adjustment are reserved by the manufacturer.
2
Pipe Parameter Entry Shortcuts
2.1
Dual Function Keys Menu Description
Press
key.
Display Flow Rate. The function is the same with
Window M02.
Press
key.
Display Velocity. The function is the same with
Window M01.
Press
key.
Display Signal Strength and Signal Quality. The
function is the same with Window M90.
Press
key.
Display Net Totalizer. The function is the same with
Window M00.
Press
key.
Display Transit Time Ratio. The function is the same
with Window M91.
Press
key.
Display System Error Code. The function is the same
with Window M08.
Press
key.
Enter Pipe Outer Diameter in Window M11.
Press
key.
Enter Pipe Wall Thickness in Window M12.
Flow 0.1129m3/h *R
POS
0x1m3
Flow 0.1129m3/h *R
Vel
1.0415m/s
SQuality [90
UP:00.0 DN:00.0 Q=00
Flow 0.1154 m3/h *R
NET 0x1 m3
TOM/TOS*100 [91
0.00%
*R------------- [08
System Normal
Pipe Outer Diameter
60.00 mm
Pipe Wall Thickness
2.00 mm