8.3 “Set-Point”, Cl (proportional)
Cl reading values can be set to operate the pH pump using 2 set-points into
On/Off mode or Proportional (%).
Proportional mode set the instrument to operate using a calculated percentage between two set values that
enable or disable the Chlorine pump. To use this mode move cursor on “Working Mode”. Press the wheel and
select it.
PROPORTIONAL mode between 1.00Cl (0%) and 0.50Cl(100%). [Stroke setting 180]
In this mode the Cl pump will be “ON” for values lower than 0.50mg/l with maximum set strokes capacity (e.g.: 180)
and it’ll be “OFF” for values greater than 1mg/l. For values of 0.75mg/l pump will be “ON” with 90 strokes capacity. The
calculation is based on 180 strokes setting (see page 22). To end procedure move cursor on “OK” and press wheel to
proceed to “Save” request screen. Move wheel on “YES” to save or “NO” to discard changes.
To end procedure move cursor on “OK” and press wheel to proceed to “Save” request screen. Move wheel on “YES” to
save or “NO” to discard changes.