Technical data 3-phase motors-English Rev.1.1 - 31-12-2005
AC INDUCTION THREE-PHASE MOTORS
Installation at altitudes of more than 1000 m above sea level (see also EN 60034-1)
Altitude of installation
2000 m
3000 m
4000 m
At 40°C ambient temperature and thermal class B
Rated output reduced to approx.
92 %
84 %
76 %
At 40°C ambient temperature and thermal class F
Rated output reduced to approx.
89 %
79 %
68 %
Full nominal output to data tables with thermal class B
and ambient temperature of
32° C
24° C
16° C
Full nominal output to data tables with thermal class F
and ambient temperature of
30° C
19° C
9° C
Starting rate
The permissible number of starts per hour can be taken as given in the table below, provided the following conditions are
met:
Additional moment of inertia
≤
moment of inertia of the rotor: load torque rising with the square of the speed up to nominal
torque; starts at even intervals.
Permissible No. of starts per hour for 2p
Shaft height
= 2
= 4
≥
6
56 - 71
100
250
350
80 - 100
60
140
160
112 - 132
30
60
80
160 - 180
15
30
50
200 - 225
8
15
30
250 - 315
4
8
12
In case a doubt for your application please consult EMCÉ, indicating
the complete operating conditions.
Ventilation
The distance between air intake of the motor and walls or other
machinery must be at least 1/4 of the diameter of the air intake opening
(not applicable for totally enclosed non ventilated motors). Cooling
airflows from the non-drive end towards the drive end. Air leaving the
motor must not be drawn in again by the fan. Keep air inlets and outlets
clean.
Connection
Choose cable cross-sections in accordance with the rated current. Not used cable entries must be closed by
compression glands.
The supply cables must be connected with special care to ensure permanent and reliable contact (without loose cable
ends); use suitable terminals for the connection cables.
Supply cables must be stress-relieved so that no cantilever loads are exerted on the terminals.
Ensure a good connection of the protective conductor.
Make sure that no foreign matter is left in the terminal box, and that it is clean and dry. Cable entries which are not used
and the terminal box itself have to be sealed dust and water-tight. In order to maintain the degree of protection, always
make sure that the original gaskets are used when closing the terminal box.
Summary of Contents for 1004156
Page 1: ...SR 30 E 1004156 Planetary Winches...
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ...3 x 4 0 0 V P E 5 0 H z 3 x 4 0 0 V P E 5 0 H z 3 x 4 0 0 V P E 5 0 H z...
Page 54: ...Manuf act urer Type Quant it y Descript ion Collector materiallist detail...
Page 55: ...Manuf act urer Type Quant it y Descript ion Collector materiallist detail...
Page 56: ...Manuf act urer Type Quant it y Descript ion Collector materiallist detail...
Page 57: ...Manuf act urer Type Comp Descript ion Quant it y Material Detail...
Page 58: ...Manuf act urer Type Comp Descript ion Quant it y Material Detail...
Page 59: ...Manuf act urer Type Comp Descript ion Quant it y Material Detail...
Page 60: ...Manuf act urer Type Comp Descript ion Quant it y Material Detail...
Page 61: ...Manuf act urer Type Comp Descript ion Quant it y Material Detail...
Page 62: ...Manuf act urer Type Comp Descript ion Quant it y Material Detail...
Page 65: ...General Manual Electric Winches with UMPH rope English Rev 1 1 10 12 2014 Notes...
Page 66: ...General Manual Electric Winches with UMPH rope English Rev 1 1 10 12 2014...