DIMM_A0 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237E92
DIMM_A1 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237DFA
DIMM_B0 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237E94
DIMM_B1 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237E0B
DIMM_C0 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237EAA
DIMM_C1 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237DF8
DIMM_D0 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237E61
DIMM_D1 Riser 3 1333 8192 18KSF1G72PDZ-1G6E1 32237E28
DIMM_A0 Riser 4 1333 16384 36KSF2G72PZ-1G6E1 DB90AD87
DIMM_B0 Riser 4 1333 16384 36KSF2G72PZ-1G6E1 DB90AD7D
DIMM_C0 Riser 4 1333 16384 36KSF2G72PZ-1G6E1 DB90ACA1
DIMM_D0 Riser 4 1333 16384 36KSF2G72PZ-1G6E1 DB90AD6F
DIMM_A0 Riser 5 1333 16384 36KSF2G72PZ-1G6E1 DB90AD85
DIMM_B0 Riser 5 1333 16384 36KSF2G72PZ-1G6E1 DB90AD84
DIMM_C0 Riser 5 1333 16384 36KSF2G72PZ-1G6E1 DB90AD76
DIMM_D0 Riser 5 1333 16384 36KSF2G72PZ-1G6E1 DB90AD88
DIMM_A0 Riser 6 1333 16384 36KSF2G72PZ-1G6E1 DB90ACAF
DIMM_B0 Riser 6 1333 16384 36KSF2G72PZ-1G6E1 DB90ACAE
DIMM_C0 Riser 6 1333 16384 36KSF2G72PZ-1G6E1 DB90ACB1
DIMM_D0 Riser 6 1333 16384 36KSF2G72PZ-1G6E1 DB90AD86
DIMM_A0 Riser 7 1333 16384 M393B2G70QH0-YK0 2151717F
DIMM_B0 Riser 7 1333 16384 M393B2G70QH0-YK0 21517146
DIMM_C0 Riser 7 1333 16384 36KSF2G72PZ-1G6E1 D96EAAA2
DIMM_D0 Riser 7 1333 16384 M393B2G70QH0-YK0 215170D1
------- ------- ------ ------- ------------------ ---------
4. Make a note of the failed DIMM information.
Shut down and disconnect the system
Procedure
1. Run the
cifs show active
and
nfs show active
commands to verify that all
I/O on the system is stopped.
2. Reboot the system to verify that no hardware issues exist on the system.
3. Stop the system using the
system poweroff
command to allow the proper shut
down of the file system and other system components.
If the system that requires a component replacement is the active node of an HA pair,
run the
ha status
command to verify that the HA pair can failover to the standby
node. Run the
ha failover
command to initiate failover to the standby node
before replacing a component. The failover process takes 10 minutes to complete.
Note
The
system poweroff
command completes when the front panel blue LED turns
off.
For help connecting to a system using a laptop computer and terminal emulator, see
the document
FE Toolkit Inventory and Common Procedures for FRU Tasks
.
4. In some cases, when you cannot use the
system poweroff
command, you can
perform a forced shut down of the system by pressing the power button for six
seconds.
Note
The power button is located in the upper right corner on the front panel of DD9500
and DD9800 systems.
DIMM and Memory Riser Card Replacement and Memory Upgrade
Shut down and disconnect the system
7