background image

62

 

 

 

Problem

 

Possible Cause

 

Repair

 

Comments

 

Water in system 

Compressed Air Inlet and 

outlet connections are reversed. 

Check inlet and outlet 

connections. 

This  dryer  is  designed  for  air  flow  in  one  direction 

only.  Inlet  and  outlet  directions  are  identified  on 

the dryer. 

 

Drain system is clogged 

or inoperative. 

 

Restore a free flow of water 

condensate. Check water 

evacuation. 

Drain system is timed solenoid valve, 

pneumatically  assisted  which  has  to  be  adjusted 

in  accordance  with  values  listed  in  this  manual. 

The Solenoid valve includes a strainer that has to be 

periodically checked and cleaned. 

Membranes  of  pneumatically assisted  drain  have  to 

be checked or replaced every 6 months. 

Bypass system is open 

Check the valves 

Important: 

Bypass  piping  should  be  installed 

around  the  dryer  so  the  dryer  can  be  isolated  for 

service  without  shutting  down  the  air  supply. 

During dryer operation, valves must be set so all air 

goes into the system. Check tightness 

of the bypass system. 

Free moisture remains in pipe lines. 

Blow out the system 

Before  the  dryer  is  first  started  all  free  moisture 

should be blown out of the system. 

Excessive air flow 

Check actual flow through the 

dryer. 

This  dryer  is  designed  for  a  maximum  air  flow. 

If too much air is pumped into the dryer, water removal 

capacity  may  not  be  sufficient,  resultingin  liquid 

Carry over downstream. Check the rated flow of the 

air compressor . 

Excessive free moisture 

Check the separator and drain 

system and compressor after 

cooler ahead of the dryer. 

In some system there may be an accumulation of free 

moisture in the line ahead of the dryer. If this moisture 

is  pumped  into  the  dryer  intermittently,  the  water 

removal capacity may not be sufficient. 

A  water  separator  should  be  installed  in  the  line 

before the dryer. 

Excessive compressed 

air inlet temperature. 

Be sure that dryer is working 

lower than design conditions 

The dryer is designed to work for calculated design 

conditions.  Should  the  conditions  be  exceeded, 

the  dryer  will  be  overflowed,  dew  point  will  go  up 

and protecting devices can switch off. 

Clogged condenser fins 

Clear fins of all obstructions 

The  clogged  fins  in  the  condenser  will  restrict  air 

passage  and  reduce  refrigerant  capacity  causing 

water  downstream.  Fins  should  be  periodically 

checked and cleaned. 

Shortage of refrigerant 

Fix the leak and add a 

charge of refrigerant. 

Loss  of  refrigerant  will  cause  improper  functioning. 

A  qualified,  refrigeration  specialist  should  perform 

the  necessary  repairs,  or  factory  should  be 

contacted if the unit is in warranty. 

 

Refrigeration system is not functioning 

Check to be certain refrigerant 

compressor is running 

To  check  if  the  compressor  is  running,  check 

compressor-on light. lt is possible for  the  fan  to  be 

operating but not the compressor. 

Compressor not running can be caused by several 

taeters.  A  qualified  refrigeration  technician  should 

check  all  refrigerant  and  electrical  controls 

Excessive pressure dew point 

Readjust refrigerant 

evaporating pressure 

The  refrigerant  pressure  adjustment  should  be 

done  by  a  qualified  refrigeration  engineer.  This  is 

a very  sensitiye  device and  incorrect  settings  may 

create other failures. 

High pressure drop 

Excessive compressed 

air flow or too law air inlet pressure. 

Check actual pressure and 

flow through the dryer. 

This  dryer  is  designed  for  a  maximum  air  flow. 

If  too  much  air  is  pumped  into  the  dryer, 

water  removal  capacity  may  not  be  sufficient, 

resulting  in  l iquid  carry-over  downstream. 

Check  the  rated  flow  of  the  air  compressor. 

Freeze up 

Check that compressor room 

ambient, 

Frosting  of  the  Iines  is  an  indication  that  controls 

are  set  too  low.  The  following  should  be  done  by 

an   experienced   ref rigeration   technician. 

Fan switch could have failed 

in closed position keeping fan 

on. 

Controls may be adjusted in the fields by means of 

the  hot  gas  bypass  valve.  This is to  be  done 

by a qualified refrigerant technician. 

 

The unit will not run or 

cycles off and on. 

 

Clogged heat exchanger 

Clean heat exchanger 

with areverse air flow. 

Dryer  are  supposed  to  be  used  with  compressed 

air  free  of  any  aggressive  contaminants.  Some 

contamination  may  require  extra  maintenance  of 

the heat exchanger. 

Line disconnect switch is 

open. 

Close the start or disconnect 

switch. 

If the dryer is not operating, check the disconnect 

switch  or  circuit  breaker  to  be  certain  it  is  on. 

 

Fuse or breaker is open 

 

Replace fuse or reset breaker. 

The fuse to the power line should be checked and 

replaced  if  needed.  Never  replace  a  burnt  fuse 

with an oversized fuse. 

Faulty refrigerant 

compressor or controls. 

Determine the cause and make 

correction 

Failure  of  compressor  to  run  may  be  caused  by 

several  factors.  A  qualified  refrigeration  specialist 

should check all electrical and refrigeration controls, 

or factory should be contacted if unit is in warranty. 

Excessive compressed air 

inlet temperature. 

Design conditions and correction 

factors are described in this manual. 

Be sure that dryer is working 

in ambient temperatures 

below design conditions. 

The dryer is designed for working into calculated design 

conditions.  Should  the  conditions  be  exceeded, 

the dryer will be overflowed, dew point will go up and 

protecting devices may trip. 

Summary of Contents for PDRCF1150029

Page 1: ...Emax Air Dryer R E F R I G E R A T E D T Y P E C O M P R E S S E D A I R D R Y E R S EDRCF1150029 EDRCF4602000 Instructions Manual ...

Page 2: ...1 3 Installation 1 1 4 Before operating 1 1 5 Maintenance by an engineer 1 1 6 Maintenance by the user 1 2 Introduction 2 3 Operation 4 4 Technical specifications 7 5 Diagrams 8 6 General Arrangements 18 7 Main Settings 18 8 Drawings 19 9 Components location 60 10 Troubleshooting 61 11 Warranty 63 ...

Page 3: ...s the following instructions need to be emphasized 1 Only authorized trained and skilled engineers should install the compressed air dryer 2 Safety devices protecting covers or insulation in the dryers never to be dismantled or modified Each pressure vessel or accessory installed outside the dryer with air above atmospheric pressure must be fitted with the required pressure relief safety valves 1 ...

Page 4: ...ompressor Expansion valve by pass valve if installed Fan pressure switch if installed 2 For water cooled dryers a Water valve b Safety high pressure switch if installed 3 The Refrigerant circuit operates as follows a The compressor compresses gaseous refrigerant to a high temperature b The hot refrigerant condenses in the condenser Being liquefied it is stored in the liquid receiver if installed c...

Page 5: ...may have migrated into the circuit during assembly e Water cooled dryers have a safety high pressure switch In case of cooling water failure the safety switch stops the dryer When the safety switch has tripped out it has to be manually resettled before switching on the dryer 8 Refrigerant circuit controls a Liquid refrigerant injection The liquid refrigerant is into the evaporator by a control val...

Page 6: ...e drop according its competitors Do not use DN US range dryers together with other dryers which have higher pressure drop without getting the confirmation from our technical team IMPORTANT NOTE The Dryer has two Compressed Air Filter inside It is better to change filter element for the best efficiency when the alarm light is active It is recommended to keep replacement filter elements in your stoc...

Page 7: ...rst stop the airflow either shut down the air compressor or close the inlet outlet or by pass valve When the air flow is stopped set the rotary switch on 0 Set it again on I in order to keep the preheating on 4 IMPORTANT NOTE Avoid leaving the dryer stopped when compressed air is still flowing through it 5 To switch the already preheated dryer on again simply push the green start button E Digital ...

Page 8: ...Emax Air Dryer REFRIGERATED TYPE COMPRESSED AIR DRYERS Technical Specifications Diagram ...

Page 9: ...28 R134a 3 232 122 140 PDRCF2300288 288 2 230 1 94 R134a 3 232 122 140 PDRCF4600288 288 2 460 1 94 R134a 3 232 122 140 PDRCF4600575 575 3 460 3 01 R134a 3 232 122 140 PDRCF2300575 575 3 230 3 01 R134a 3 232 122 140 PDRCF4600850 850 3 460 4 31 R134a 3 232 122 140 PDRCF4601200 1200 3 460 5 68 R134a 3 232 122 140 PDRCF4601600 1600 3 460 R134a 3 232 122 140 PDRCF4602000 2000 3 460 R134a 3 232 122 140 ...

Page 10: ...8 5 1 AIR FLOW DIAGRAMS EDRCF1150029 EDRCFR1150144 M IMPORTANT NOTICE 5 Only From Dryer PDRCF1150115 to PDRCF1150144 9 Only from Dryer PDRCF1150115 to PDRCF1150144 ...

Page 11: ...9 ...

Page 12: ...10 5 2 ELECTRICAL DIAGRAMS Dryair DN10 US Dryair DN30 US ElectricalCircuit ...

Page 13: ...12 Dryair DN40 US Dryair DN80 US Electrical Circuit ...

Page 14: ...15 Dryair DN100 US Dryair DN110 US ElectricalCircuit ...

Page 15: ...16 Dryair DN140 US Dryair DN170 US Electrical Power Circuit ...

Page 16: ...Emax Air Dryer REFRIGERATED TYPE COMPRESSED AIR DRYERS General Arrengements Main Settings Drawings ...

Page 17: ...yairDN120 US 1 GKO1210X 1 GKO1210Y MKO1210KIT 37 32 28 66 53 94 484 DryairDN130 US 1 GKO1210X 1 GKO1210Y MKO1210KIT 37 32 28 66 53 94 506 DryairDN140 US 1 GKO1820X 1 GKO1820Y MKO1820KIT 37 32 31 42 57 48 594 DryairDN150 US 1 GKO1820X 1 GKO1820Y MKO1820KIT 37 32 31 42 57 48 627 DryairDN160 US 1 GKO2700X 1 GKO2700Y MKO2700KIT 45 79 30 63 67 91 862 40 DryairDN170 US 1 GKO2700X 1 GKO2700Y MKO2700KIT 4...

Page 18: ...19 Dryair DN10 US Dryair DN30 US 8 ED and ID DRAWINGS ...

Page 19: ...20 Dryair DN40 US Dryair DN60 US ...

Page 20: ...21 Dryair DN70 US Dryair DN90 US ...

Page 21: ...22 Dryair DN100 US Dryair DN110 US ...

Page 22: ...23 Dryair DN140 US Dryair DN150 US ...

Page 23: ...24 Dryair DN160 US Dryair DN170 US ...

Page 24: ...25 Dryair DN30 US ...

Page 25: ...26 Dryair DN50 US ...

Page 26: ...27 Dryair DN70 US ...

Page 27: ...28 Dryair DN80 US ...

Page 28: ...29 Dryair DN110 US ...

Page 29: ...30 Dryair DN140 US ...

Page 30: ...31 Dryair DN160 US ...

Page 31: ...32 Dryair DN170 US ...

Page 32: ...60 9 COMPONENTS LOCATION ...

Page 33: ...ting devices can switch off Clogged condenser fins or clogged watercondenser Possible high crankcase temperature Possible loss of phase Possible low voltage causing overload trip Possible failed compressor Clear fins or water condenser of all obstructions The clogged fins in the condenser will restrict the air passage and reduce the refrigeration capacity causing high temperature in the evaporator...

Page 34: ...ould be contactedif the unit is in warranty Refrigeration system is not functioning Check to be certain refrigerant compressor is running To check if the compressor is running check compressor on light lt is possible for the fan to be operatingbut not the compressor Compressor not running can be caused by several taeters A qualified refrigeration technician should check all refrigerant and electri...

Page 35: ...gn occurs on digital temperature control device The dew point is too low or too high Check refrigerant gas and make sure that the working conditions are within the cor rect range If there is not enough refrigerant gas or if the working temperature and inlet temperatures are very high the dew point will increase Refrigerated Dryer WARRANTYPOLICY When used under the conditions recommended the heat e...

Reviews: