Replacing ion exchanger resin 

a)  Empty the used resin

If  the  content  of  dissolved  solids  in  the  treated  water  exceeds  30  TDS  (approx.  2  °fH)  according  to  the 
meter, then the resin must be changed. We first recommend that you briefly interrupt the water supply, 
shake the cartridge and then slowly turn the water supply back on and fill-up. Thus the residual capacity 
can be as exhausted as well as possible.

Close ball valve 1) and 2) in the cartridge inlet and outlet. Leave PUROTAP profi connected to the 
untreated water tap 3).

Connect  hose  to  the  drain  valve  4)  and  insert  it  into  the  supplied  water-permeable  collection 
sack. Tightly connect the sack to the top of the hose with a cable binder or tape.

Open the drain valve 4).

Open ball valve 1) in the inlet.

Let the resin drain out and then close the ball valve in inlet 1) again.

Let the cartridge have a dry run and close the drain valve 4).

If the collection sack is dripping with resin, then dispose of it in the household waste.

1.

2.

3.

4.

5.

6.

7.

Open  the  drain  valve  on  the  cartridge 
only when replacing the resin and only 
if a hose is connected to the collection 
sack.  Under  no  circumstances,  do  not 
connect the drain valve to a water sup-
ply system.

 

Empty

Summary of Contents for PUROTAP profi

Page 1: ...al water circulationslead to corrosion and mineral deposits PUROTAP filters aggressive materials out of the water and enables trouble free operation Installation Function Operation Service Demineralis...

Page 2: ...ing to the latest standards Connection The instruments Determining water hardness Calculating capacity Replacing ion exchanger resin TDS meter malfunction Changing batteries Flow rate measurement devi...

Page 3: ...he filling apparatus Operating specifications must be adhered to according to this manual Local guidelines are to be followed for the connection between sanitary and heating sys tems The device alread...

Page 4: ...m the water supply company PUROTAP profi may only be under pressure for the duration of the filling process A permanent con nection under pressure is not permitted Temp max 60 C Pressure max 6 bar Cle...

Page 5: ...a the measuring value in the input and the capacity of the resin can be calculated In order to conserve batteries the meter turns off automatically after 20 seconds Reset if necessary The current fill...

Page 6: ...ard hard hard very hard very hard 75 150 225 300 375 450 575 600 675 750 825 900 50 100 150 200 250 300 350 400 450 500 550 600 3 8 7 5 11 3 15 0 18 8 22 5 28 5 30 0 33 8 37 5 41 5 45 0 g g g g g g g...

Page 7: ...e untreated water tap 3 Connect hose to the drain valve 4 and insert it into the supplied water permeable collection sack Tightly connect the sack to the top of the hose with a cable binder or tape Op...

Page 8: ...ak into the system 1 2 3 4 5 Make sure that no resin ends up on the floor This represents a significant slipping hazard Carefully and thoroughly remove leaked resin off the floor e g with the vacuum c...

Page 9: ...vice and sensormustbereplaced Check the water meter to see whether the refill station is full of water If this is the case then this is not a malfunction instead it is a correct measurement of the des...

Page 10: ...cartridgeisblocked Loosenscrew rinseoutfinesieveandreattach Malfunction Solution Plastic ring pressed in Plastic ring pressed in Stainless steel sieve Das Restwasser im Harzbeh lter und in den Leitung...