elysator PUROTAP profi Installation Function Operation Service Download Page 3

4

Heating and cooling systems use water as a medium for heat transfer. The water circulates from where the 
warm water is generated to the user and back. Even if the system always re-uses the same water, lime and 
aggressive materials enter the closed water system when first filling the system, which can damage modern 
components.

The filling apparatus filters lime and aggressive dissolved substances such as sulfate, nitrate and chloride out 
of the fill-up water. The device operates on the basis of a mixed bed ion exchanger and provides demineral-
ised water that has been completely desalinated. Thus, damage caused by lime and corrosion can be effec-
tively prevented in the heating system. 

The filling apparatus is equipped with precise meters for monitoring pure water production in terms of qual-
ity and quantity.

This method does not release any chemical additives into the water.

The device operates without an external power supply.

If the ion exchange capacity is exhausted, then the ion exchange resin can be easily replaced and disposed of 
with the household waste.

Protective
measures

Only trained personnel should use the filling apparatus.

Operating specifications must be adhered to according to this manual.

Local guidelines are to be followed for the connection between sanitary and heating sys-
tems. The device already has a return and pressure-reducing valve. In the DIN EN 1717 
(Germany) field of application, a pipe disconnector must also be installed before the fill-
up station.

The system is not suitable for unmonitored, permanent connection under pressure. The 
valves in the input and output are to be kept closed and only to be opened for the dura-
tion of the system filling.

Even demineralised water contains dissolved gasses, including oxygen and carbon diox-
ide that can cause the beginning of a corrosion process. The gases are purged by heating 
the water, therefore we recommend carrying out a heating test run for the system as 
soon as possible after fill-up.

Leading boiler manufacturers and component suppliers approve and recommend the procedure for purging 
make-up water via the ion exchanger.

The demineralised make-up water as a result of desalination also fulfils the requirements for heater fill-up 
water quality according to VDI guideline 2035 (Association of German Engineers), the SWKI guideline 
BT 102-01 (Swiss Heating and Air Conditioning Engineers) and the Ö-Norm H5195.

PUROTAP profi function

According to the latest standards

Summary of Contents for PUROTAP profi

Page 1: ...al water circulationslead to corrosion and mineral deposits PUROTAP filters aggressive materials out of the water and enables trouble free operation Installation Function Operation Service Demineralis...

Page 2: ...ing to the latest standards Connection The instruments Determining water hardness Calculating capacity Replacing ion exchanger resin TDS meter malfunction Changing batteries Flow rate measurement devi...

Page 3: ...he filling apparatus Operating specifications must be adhered to according to this manual Local guidelines are to be followed for the connection between sanitary and heating sys tems The device alread...

Page 4: ...m the water supply company PUROTAP profi may only be under pressure for the duration of the filling process A permanent con nection under pressure is not permitted Temp max 60 C Pressure max 6 bar Cle...

Page 5: ...a the measuring value in the input and the capacity of the resin can be calculated In order to conserve batteries the meter turns off automatically after 20 seconds Reset if necessary The current fill...

Page 6: ...ard hard hard very hard very hard 75 150 225 300 375 450 575 600 675 750 825 900 50 100 150 200 250 300 350 400 450 500 550 600 3 8 7 5 11 3 15 0 18 8 22 5 28 5 30 0 33 8 37 5 41 5 45 0 g g g g g g g...

Page 7: ...e untreated water tap 3 Connect hose to the drain valve 4 and insert it into the supplied water permeable collection sack Tightly connect the sack to the top of the hose with a cable binder or tape Op...

Page 8: ...ak into the system 1 2 3 4 5 Make sure that no resin ends up on the floor This represents a significant slipping hazard Carefully and thoroughly remove leaked resin off the floor e g with the vacuum c...

Page 9: ...vice and sensormustbereplaced Check the water meter to see whether the refill station is full of water If this is the case then this is not a malfunction instead it is a correct measurement of the des...

Page 10: ...cartridgeisblocked Loosenscrew rinseoutfinesieveandreattach Malfunction Solution Plastic ring pressed in Plastic ring pressed in Stainless steel sieve Das Restwasser im Harzbeh lter und in den Leitung...

Page 11: ...12 Journal Date Resin changed 3 top meter m TDS in TDS out...

Reviews: