CMe2100 LTE Quick manual A4 English

Version:  1.3  

Mechanics

Protection class

IP20

Mounting

Mounted on DIN rail (DIN 50022) 35 mm

SIM card

Push-push type

Electrical connections

Supply voltage

Screw terminal. Cable 0.5-2.5 mm², 0.5 Nm 

tightening torque

M-Bus master port

Screw terminal. Cable 0.2-1.5 mm²

Electrical characteristics

Nominal voltage

100-240 VAC (+/- 10%)

Frequency

50/60 Hz

Power consumption (max)

<6 W

Power consumption (nom)

<1 W

Installation category

CAT 3

User interface

Green LED

Power

Red LED

Error

Yellow LED

Network status

Push button

Factory reset

Configuration

SMS, HTTP, Telnet

Integrated M-Bus Master

M-Bus baud rate

2400 and 9600 bit/s

Nominal voltage

28 VDC

Maximum unit loads

16T/24 mA 

Maximum cable length

1000 m (100 nF/km, maximum 90 

Ω

)

Approvals

EMC

EN 61000-6-2, EN 61000-6-3, EN 301489-

1, EN 301489-7

Safety

EN 61010-1, CAT 3

ORDERING INFORMATION

CONTACT INFORMATION

Elvaco AB Technical support:

Phone: +46 300 434300 
E-mail: support @elvaco.com 
Online: www.elvaco.com

TECHNICAL SPECIFICATIONS

n: the number of meters to be installed  
[profile]: customer specific profile with custom settings (contact Elvaco 
to order a profile). Default settings will be used if no customer specific 
profile is set. 
[secondary address]: secondary address of the meter to be read. If only 
one meter is connected, the secondary address can be omitted.An SMS 
from the product should be received within a minute with information 
that the installation has started. The product will also send an SMS with 
information about if the installation was successful or not. 
For a successful installation, the signal strength should be at least 3.

TROUBLESHOOTING

All LEDs are permanently off

 

There is a problem with the supply voltage. Please verify 100-240 VAC. 
If the problem persists, the product may be malfunctioning. Please 
contact Elvaco support.

Red LED is permanently on

 

This indicates an error on the M-Bus 2-wire bus. Please verify no short-
circuit of the M-Bus bus. The voltage of the bus should be between 24 
VDC and 30 VDC.

Red LED is flashing shortly or 50/50

 

This indicates an error on the networks or SIM card.  
Please verify:
• 

SIM card has no PIN code activated. 

• 

SIM card is activated.

• 

SIM card contact areas are clean.

• 

Antenna installation. Installation with bad network coverage 
sometimes requires an external antenna.

The product does not respond to SMS requests

 

Please verify:
• 

Product is powered up.

• 

LEDs are showing normal operation and network coverage.

• 

Security access codes may be used; verify correct access code.

• 

If a prepaid SIM card is used, balance may be zero.

Install command does not find any meters

 

Please verify your M-Bus slave configuration:
• 

Voltage over M-Bus slave should be between 24 VDC and 30 VDC.

• 

All M-Bus slaves must have unique primary or secondary M-Bus 
addresses depending on addressing mode.

• 

M-Bus slave baud rates.

Timesync command does not work

 

This may be due to wrong APN is set. Set the correct APN with the 
command: qset net [APN][user][password]. Please contact your 
network provider for information about APN, APN username and APN 
password.

E-Mail reporting is configured but no e-mails are sent

 

This may be due to the following reasons, when customer specific profile 
is not used:
• 

No or wrong SMTP server is auto detected. Please verify with 
command status. If the SMTP server is not set, please set the SMTP 
server manually by using command qset email [recipient] [SMTP-
server] [SMTP-port].

• 

No/no valid recipients are set. Set recipients with command qset 
email [recipient].

• 

Report is not correctly activated, please configure e-mail reports 
with command sch (see table).

SAFETY

The warranty does not cover damage to the product caused by usage in 
any other way than described in this manual. Elvaco AB can not be liable 
for personal injury or property damage caused by usage in any other way 
than described in this manual.

Product

Item number

Description

CMe2100 LTE

1100386

1 M-Bus meter

CMe2100 LTE

1100363

16 M-Bus meter (16T)

CMe2100 LTE 

1100364

32 M-Bus meters (16T)

CMe2100 LTE

1100365

64 M-Bus meters (16T)

CMe2100 LTE

1100366

128 M-Bus meters (16T)

CMe2100 LTE

1100367

256 M-Bus meters (16T)