8. Use appropriate copper wire with listed
pressure terminal connectors, such as
conductor before attachment to the terminal
blocks. Keep enough length of wire to
facilitate installation. Connect each terminal
to the correct terminal input block
connector in the compartment and torque
to 19 lb•in (2.2 N•m) .
Note:
Model
Copper wire type
CH-21140
No. 6 AWG, 90 ºC
CH-21130
No. 8 AWG, 75 ºC
or 90 ºC
Note: Choose appropriate conduit in
accordance with all applicable state, local and
national electrical codes and standards.
9. Replace the compartment cover and torque
to 8.7 lb·in (1.0 N·m).
10. Replace the front cover by aligning the
hinge on the top. Secure the front cover
by the bottom screw, torque to 10.4 lb·in
(1.2 N·m).
11. Place the charger cable properly.
To view an introduction installation video, visit www.gridcharge.io
Installation-manual_CH-211