Technical data
page 34
ELTROPLAN-REVCON
3.3.4
Fuses and wire cross sections
The power feedback unit is connected to mains supply via the terminals L
1
-L
3
at the
commutation choke and PE at the heatsink. Mains fuses must be designed according to the
current load capacity of the supply wire.
3.3.4.1
Series fuses
Semiconductor fuses have to be connected in series with the power feedback unit as following
tables (refer to figure 4.4.1.1.1 position 1). The listed manufacturer is recommended, but natu-
rally also comparative fuses of other manufacturer (e.g. Jean Müller, Ferraz, Bussmann) are
suitable.
REVCON
®
- type
max. fuse AC
Connection terminal and max.
cross section of the supply line *
SVCS 7-400-1-0
Siba 50 179 06 20A 660V 10*38mm
CS M5
25mm²
SVCS 13-400-1-0
Siba 50 124 06 30A 690 V 14x51mm
CS M6
35mm²
SVCS 22-400-1-0
Siba 50 124 06 50A 690 V 14x51mm
CS M6
35mm²
SVCS 33-400-1-0
Siba 50 140 06 80A 690 V 22x58mm
CS M6
35mm²
Table 3.3.4.1.1
ES
≅
end sleeve for strands
CS
≅
cable socket with drill hole for M6 / M8 / M10
* at the copper lug of the commutation choke.
** at the fuse holder respective disconnector