Technical data
ELTROPLAN-REVCON
page 29
3.3
Rated data
3.3.1
Power feedback unit
REVCON type
SVC(S) 400V
Nominal range of the
interlinked mains voltage
U
N
[V]
380
≤
U
N
≤
415
Tolerance of the
interlinked mains voltage
U
N
[V]
342
≤
U
N
≤
456
Mains frequency
f
N
[Hz]
50
±
2 %
Overload capability
ca. 1,2 x Irms (dynamic)
Efficiency
η
[%]
Ca. 96 % (4 % therm. losses)
Power factor*
3
cos
ϕ
∼
1
Total harmonic distortion*
3
THDI
[%]
< 16%
*
1
need of airflow
m³ / h
a)
SVCS 7-400, 13-400, 22-400,
:
200
b)
SVCS 33-400
:
350
Power derating
[%/K]
[%/m]
40°C < Ta < 55°C
⇒
3%/K
1000m a.m.s.l.< h
≤
4000m a.m.s.l.
⇒
5%/1000m
Table 3.3.1.1
*
1
depending on the size of the unit ( nominal power and nominal voltage)
*
2
alternative case-type with minor changed dimensions
*
3
at nominal current