Quick guide for TBA firmware V1.070
Description of the displayed parameters
(figure 17)
:
„Q” - charge collected from the discharging battery
„V” - average voltage value per cell
„U” - present voltage of the discharging battery
„c” - battery efficiency coefficient (%) [(Q/Q5) x 100%]
„t” - discharge time which increases or decreases depending on the
“Counter Settings”
„G” - the number of enabled resistors enforcing the discharge current
„T”k - resistance chamber temperature
The discharge is over when either the battery voltage achieved the
set value „Vk”
(figure 18)
or the set discharge time was over „t”
(figure 19)
.
Blowing is on for 3 minutes after the end of the discharge. The blowing
process allows for faster cooling of resistors.
When the blowing time is over, the display will show the information
on the discharge end reason: „U” - when the set final voltage of the
„Vk” cell achieved the set value
(figure 20)
or „t” - when the set discharge
time was over
(figure 21)
.
Press the [F1] „End” button to return to the main menu of the tester.
At any moment of the discharge process you may turn off the discharge
current by pressing the [OFF] (red) button.
This possibility should be treated as a temporary halt to the discharge
process.
Press the [ON] (green) button to reactivate the discharge process.
To permanently finish the discharge process, press the F1 [End] button.