3. Installation and assembly
3.1 Assembly the power supply
The power supply must be installed outside the explosion hazard area.
The power supply is designed for wall mounting. Attach using the brackets
provided (installation dimensions, see Fig. 2). The operating elements of
the power supply and the terminals must be freely accessible at all times
and the display LEDs must be visible.
3.2 Ground connection
A permanent ground connection must be made via the grounding terminal
(6, Fig. 1). The ground cable should have a minimum cross section of
1.5 mm
2
.