Service menu
2280073 Rev.1
Page 33
Structure of service menu
0
1
Set voltage
Service menu
code:0000
Set
mode
Activate
24V mode
Present mode
Charging Pb
Present mode
Charging LIO
Present mode
EPS 12V
Present mode
EPS 24V
Present mode
EPS autostart
24V mode off
24V mode on
Set 12V Pb
trickle voltage
Trickle Pb
Now at: 13.4V
Set 12V LIO
trickle voltage
Set 24V
trickle voltage
Trickle 24V
Now at: 26.8V
Set 12V Pb
charging voltage
Charging Pb
Now at: 14.8V
Set 12V LIO
charging voltage
Set 24V
charging voltage
Charging 24V
Now at: 28.8V
Set U-Shutdown
Set U-Refresh
Set 12V
EPS voltage
Set 24V
EPS voltage
Exit menu
EPS 12V
Now at: 14.2V
EPS 24V
Now at: 28.0V
Set voltage limit
Set Ua max.12V
Ua max.12V
now at: 16.0V
Set Ua min.12V
Ua min.12V
now at: 7.0V
Set Ua max.24V
Ua max.24V
now at: 32.0V
Set Ua min.24V
Ua min.24V
now at: 14.0V
Exit menu
U=00.0V I=0.0A
Pb no contact
Present mode
Charging Pb
Present mode
Charging LIO
Taste
Trickle LIO
Now at: 13.4V
Charging LIO
Now at: 14.0V
U-Shutdown
Now at: 11.0V
U-Refresh
Now at: 14.0V
Present mode
LIO Batt Refresh