10.5
Output-current limits (I-limits)
The
"Set current limit"
menu is used to set the level of the MC1500's maximum nominal
current. The MC1500 can constantly deliver whatever current level is entered here. In the
battery-charging mode, this level can also be exceeded by 25% for a maximum period of 1min.
10.5.1 Set I-limit CHRG12V
This is a sub-item of the
"Set current limit"
menu. It is used to set the MC1500's maximum
nominal current for the 12V battery-charging mode.
Default setting: 80.0A/100A
Setting range: 0.0A to 80.0A/100A
10.5.2 Set I-limit CHRG24V
This is a sub-item of the
"Set current limit"
menu. It is used to set the MC1500's maximum
nominal current for the 24V battery-charging mode.
Default setting: 40.0A/50A
Setting range: 0.0A to 40.0A/50A
10.5.3 Set I-limit EPS 12V
This is a sub-item of the
"Set current limit"
menu. It is used to set the MC1500's maximum
nominal current for the 12V external power supply mode.
Default setting: 80.0A
Setting range: 0.0A to 80.0A
10.5.4 Set I-limit EPS 24V
This is a sub-item of the
"Set current limit"
menu. It is used to set the MC1500's maximum
nominal current for the 24V external power supply mode.
Default setting: 40.0A
Setting range: 0.0A to 40.0A