24
User Guide •
Smartpack S Controller
About Power System Configuration
350030.013, 1v0-2012-06
8 - Up/Download options (Data Storage Device)
The options in this logical group let you upload firmware from the controller’s data
storage device to connected controllers and control units, as well as download or
save system related logs, etc. to the data storage device.
Notice:
The
Smartpack2 Master
controller uses an external SD card as data storage device, and the
Smartpack S
controller uses embedded Flash Memory.
In addition to firmware, this group’s options offer you the possibility of uploading
and saving system configuration files to controller’s data storage device.
Uploading and downloading is allowed at this level, using the Pin-Code for the Ser-
vice Access Level
.
Notice:
Using the
WebPower
or
PowerSuite
you can also up/download to other storage media (e.g.
computer hard discs)
The Up- and Download options are organized in following groups:
• Save Event Log
(system related log)
A command that saves to the controller’s data storage device a log of
power system events automatically registered by the system control-
ler.
Read about
"Logs and Reports options" on page 22
• Save Data Log
(control unit related log)
A command that saves to the controller’s data storage device a log of
key system data (voltages, current and temperature values) registered
by the system controllers, or by other connected control units (e.g. I/O
Monitor, Mains Monitor)
• Save Energy Log
(system related log)
A command that saves to the controller’s data storage device a log of
the power system’s energy usage, (Wh).
• Save /Load Config
A command that saves to the controller’s data storage device a binary
formatted file <UNIT_nn.HEX> which contains the controller’s or any
connected CAN unit’s System Configuration, with all the specific pa-
rameters and settings.
Also, you can upload a similar, specific System Configuration file
<UNIT_nn.HEX> to the controller or to any connected CAN unit, e.g. for
automatic configuration of specific functions
The “nn” in the file name specifies the unit’s CAN bus address.