16
User Guide •
Smartpack S Controller
The Smartpack S Controller
350030.013, 1v0-2012-06
Technical Specifications
Model
Smartpack S
Part number
242100.410
INPUT DATA
Voltage (nominal)
10 - 75 VDC
Power Consumption, max - no relays energized
max - all relays energized
TBD W
TBD W
SYSTEM CONNECTIONS - SYSTEM MONITORS
Voltage sense, system voltage support
12 VDC, 24VDC, 48VDC & 60VDC
Current sense, shunt support
0 - 20mV and 0 - 60mV
Battery fuse monitoring
Auxiliary switch NO/NC, Pull up/down
Load fuse monitoring
Auxiliary switch NO/NC, Diode Matrix Pull up/down
Ground fault detection
Simple bridge circuit detection
SYSTEM CONNECTIONS - LVD CONTROL
Battery disconnect
1 (latched or non-latched supported)
Load disconnect
1 (latched or non-latched supported)
INPUTS AND OUTPUTS
Digital configurations, Inputs #1-6
Auxiliary switch: NO/NC, Pull up/down
Analog configurations, Inputs #1-4
Analog Voltage[±0 - 10V]
±4-20mA current measurement (through external 470kΩ resistor)
Temperature (for NTC probe)
Analog configurations, Inputs #5-6
Analog Voltage[0-75V]
Symmetry measurement
Output configurations, Outputs #1-6
(alarms)
6x Relay–Dry/Form C
Configurable Normally Open/Closed
[Max capacity 75V/2A/60W]
USER INTERFACE
Local
2.2” TFT 65k Colour display
QVGA resolution
4 keys
Ethernet port
10/100 BASE-T
HP Auto MDI/MDI-X
IP protocols: HTTP / SSL, SNMP v3, MODBUS TCP and pComm UDP
(
PowerSuite
)
Serial port
RS-232 or RS-485 on RJ11 connector
Serial protocols (pending): MODBUS RTU, Modem Call-Back/SMS
reporting (PSTN or GSM) and CSCP
GENERAL SPECIFICATIONS
Dimensions (WxHxD)
72.2 x 43.0 x 220.7mm (2.8 x 1.7 x 8.7”)
Temperature Range
Operating -20 to +60˚C (-40 to 140˚F)
DESIGN STANDARDS
Electrical safety
UL 60950-1-3rd edition, EN 60950-1-3rd edition
EMC
ETSI EN 300 386 V.1.4.1
EN 61000-6-1 / -2 / -3 / -4
FCC Part 15 Subpart 109
Marine*)
DNV- OS-D202, Ch.2 Sev.4 (DNV 2.4), Temperature Cl. B, Humidity Cl.
B, Vibration Cl. A and EMC Class B
Environment
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
ROHS compliant
*) As part of CA0603.000 Flatpack S 3U Marine system
Specifications are subject to change without notice
Doc 242100.410.DS3 – v1