Eltako – The System in the Building – Operating manual for Series 14 RS485 bus DIN rail mounted devices
28
Powerline Gateway FPLG14
Teach-in wireless sensors via rotary switches:
Set the middle rotary switch to the desired group address g. Set the upper-right rotary switch to the desired elementary address e.
Set the lower rotary switch to the required teach-in function. Press the button to be taught in twice quickly in succession ('double
click'). The LED goes out.
Teaching-in a pushbutton of a Powerline sensor input into RS485 bus actuators:
At first, check that the PL-module has an adress (g) and (e). Select the desired teach-in function at the bus-
actuator using the upper rotary switch (for FSR14 and F4HK14, set the lower rotary switch to the desired channel).
Set the middle rotary switch to LRN. The LED flashes at a low rate. Operate the pushbutton. The LED goes out.
To teach-in PL telegrams generated from the Software Sienna-Professionnal into a RS485 bus actuator, the lower rotary switch
must be on AUTO/LRN.
Address assignment via PCT14:
The HEX address assigment results from the group address (g) and from the element address (e).
This table shows how to translate the addresses into HEX numbers.
Group address into HEX number:
(g)
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
-
HEX
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
-
Element address into HEX
:
(e)
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
HEX
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
More addresses are available with the software Sienna
®
-Professional
(e)
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31 bis 127
HEX
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F bis 7F
PL-Sensor-Telegrams
for pushbuttons and control commands: range: 00004100 - 00004F7F
The base ID
00004
is always present additionally to the group and element adresses 00004(g)(e)
Example:
Group address A and element address 1
00004
1
01
Group address D and element address 12
00004
4
0C
Group address F and element address 127
00004
F
7F
PL-Actuator-State-Telegrams for feedback:
range: 00005
100
– 00005
F7F
The base ID 00005 is always present additionally to the group and element adresses 00005(
g
)(
e
)
Example:
State telegram from the PL module with group address A and element address 1
00005
1
01
State telegram from the PL module with group address O and element address 15
00005
F
0F
Settings in operation mode:
In operation, the left and lower right rotary switches must be placed on AUTO.
LED in operation mode:
Signal transits over the gateway are shown by the LED. The red LED from the upper right rotary switch is showing the wireless telegrams.
The green LED from the lower rotary switch is showing the Powerline telegrams.