background image

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. 

Confirmation of dimensions and data will be supplied on request.

5

REVOLUTION SLC

Installation Instructions

GND

10V

E1

MIN

MAX

E1

GND

ST1

ST2

ST2

E1

10V

GND

MAX

MIN

ST1

GND

E1

THE ABOVE DIAGRAM SHOWS "ST2".

"ST2" CONNECTIONS ARE FACTORY FITTED.

GND

 = COMMON

10V

 = 10VDC INPUT

E1

 = 0-10VDC OUTPUT

YOU CAN DETERMINE THE CURRENT VDC OUTPUT BY
DISCONNECTING POWER TO THE UNIT, SETTING A
MULTIMETER TO OHMS (Ω) AND PLACING THE TEST PROBES
BETWEEN GND AND E1

PLEASE USE THE ESTIMATED ADJUSTMENT GUIDE FOR REFERENCE

THIS IS THE INTERNAL POTENTIOMETER
THIS POTENTIOMETER CAN BE ADJUSTED FOR SINGLE SPEED 
SETTING OR MAX SPEED SELECTION

THIS LINK/JUMPER SHOULD BE REMOVED
WHEN USING AN EXTERNAL POTENTIOMETER
OR EXTERNAL CONTROL SIGNAL CONNECTED
TO "ST1"

THE ABOVE DIAGRAM SHOWS "ST1".

"ST1" CONNECTIONS ARE CLASSED AS
"CUSTOMER/USER CONNECTIONS".

GND

 = COMMON

+

 = VDC OUTPUT AS SET BY


                 INTERNAL POTENTIOMETER

E1

 = 0-10VDC INPUT

149-CD-POT

10/07/2018

MK-149-CD-POT

Issue:

Saved Date:

A

All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. 

149-CD-POT Issue A: 10.07.2018

Check the individual product accessories table for fan controller compatibility.

149-CD-POT

The 149-CD-POT is a commissiong device designed to be used with our EC range of fans. 

The device will allow the for the installer to set the maximum operating speed of the fan that it is connected to.  

The installer or commissioning engineer can adjust the fan speed using the potentiometer built onto the 149-CD-POT board. 

This potentionmeter can either be used for single speed adjustment or to set a maximum speed for the fan to operate at when an external control 

source is used. 

If external speed control is required, the jumper connection next to the potentionmeter on the board would need to be removed, the installer can 

then connect to ST1 (using the diagram provided). 

When an external speed control is fitted, the maximum speed setting available to the external control is limited by the potentiometer setting of the 

commissioning device.

EC

Please note: This is an estimated adjustment guide

149-CD-POT

The 149-CD-POT is a commissiong device designed to be used with our EC range of fans.

This device will be as standard with our box fan range from May 2018.

The device will allow the for the installer to set the maximum operating speed of the fan that it is

connected to.

The installer or commissioning engineer can adjust the fan speed using the potentiometer built onto the

149-CD-POT board. This potentionmeter can either be used for single speed adjustment or to set a

maximum speed for the fan to operate at when an external control source is used.

If external speed control is required, the jumper connection next to the potentionmeter on the board
would need to be removed, the installer can then connect to ST1 (using the diagram provided).

When an external speed control is fitted, the maximum speed setting available to the external control is

limited by the potentiometer setting of the commissioning device.

10/07/2018

MK-149-CD-POT

Issue:

Saved Date:

A

Level / Speed

OHMS (Ω)

10

10 (Ω)

9

9 (Ω)

8

8 (Ω)

7

7 (Ω)

6

6 (Ω)

5

5 (Ω)

4

4 (Ω)

3

3 (Ω)

2

1.5 (Ω)

1

500 (Ω)

0

1 (Ω)

149-CD-POT

Summary of Contents for Revolution SLC Series

Page 1: ...These instructions must be read fully before commencing installation REVOLUTION SLC Installation Maintenance...

Page 2: ...ation 2 3 The fan must be securely mounted in the desired position to suit the application The fan can be mounted at any angle 2 4 Check the details on the motor rating plate to ensure that the correc...

Page 3: ...r 4 2 All fastenings should be checked for tightness In addition all rotating items should be checked 4 3 Bearings are of the sealed for life type and will not need a detailed inspection WARNING Fuses...

Page 4: ...RAWING No SHEET OF DRAWN BY DATE SCALE STATUS APPROVED CHECKED FINISH MATERIAL SPECIFICATION DIMENSIONS ARE IN mm UNLESS STATED OTHERWISE THIS IS A C A D PRODUCED DR AND THEREFORE NO SUBSEQ MANUAL MOD...

Page 5: ...it is connected to The installer or commissioning engineer can adjust the fan speed using the potentiometer built onto the 149 CD POT board This potentionmeter can either be used for single speed adj...

Page 6: ...SLC500 4A 3AC 152 600 8 SLC500 4B 3AC 152 600 9 SLC560 2 3AC 152 601 8 SLC560 4A 3AC 152 600 8 SLC560 4B 3AC 152 600 8 SLC560 4C 3AC 152 600 8 SLC630 4A 3AC 152 600 8 SLC630 4B 3AC 152 600 8 SLC710 4A...

Page 7: ...rmation of dimensions and data will be supplied on request 7 Single Phase 220V 277V 50Hz or 60Hz Page No Product Code Wiring Diagram No 10 SLC315 1EC 152 710 10 SLC355 1EC 152 710 10 SLC400 1EC 152 71...

Page 8: ...TC18 TC110 TC112 BROWN BROWN BLUE GREEN YELLOW E L N CONTROLLER TERMINAL BOX GREEN YELLOW BROWN BLUE REMOVE LINK BETWEENU1 Z2 Z2 U1 Z1 U2 CAP1 CAP2 220 240V 1PH 50Hz SUPPLY AUX N L N L E E N L Z2 U1 Z...

Page 9: ...GREY BLACK BROWN 4 5 6 7 3 1 2 8 11 10 9 L1 L U V W L3 L2 N BROWN BLACK GREY GREEN YELLOW BROWN BLACK GREY GREEN YELLOW 1TO7 PRE WIRED E L1 FAN TERMINAL BOX 380 440V 3PH 50Hz SUPPLY L2 10 RELAY COMMON...

Page 10: ...Y CONTACT L3 ANALOG DIGITAL INPUT CONNECTIONS 3PH 3PH IP55 INVERTER L2 380 440V 3PH 50Hz SUPPLY FAN TERMINAL BOX L1 E GREEN YELLOW GREY BLACK BROWN W2 U2 V2 U1 W1 V1 GREEN YELLOW GREY BLACK BROWN 3PH...

Page 11: ...POT 10 SINGLE FAN N L 220 277V 1PH 50 60Hz MAINS SUPPLY BROWN BLUE G Y YELLOW WHITE BLUE RED CONTROLS POWER L N PE MAX SPEED TRIMMER JUMPER REMOVED BROWN BLACK 5 6 FOR USEWITH SLC315 1EC SLC350 1EC S...

Page 12: ...Tel 01384 275800 Fax 01384 275810 Email bs eltafans co uk Website eltafans com 12 Notes REVOLUTION SLC...

Page 13: ...oduct development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication Confirmation of dimensions and data will...

Page 14: ...rd West Midlands DY6 7US United Kingdom Tel 44 0 1489 566500 Fax 44 0 1489 566555 Email at eltafans co uk export eltafans co uk 17 Barnes Wallis Road Segensworth East Industrial Estate Fareham Hampshi...

Reviews: