Installation Instructions
REVOLUTION SLC
1.0
General
1.1
It is important these Installation and Maintenance Instructions are fully adhered to.
1.2
Full details of the unit supplied are shown on the product nameplate. If in doubt about any detail contact Elta Fans Ltd or its agents for
clarification.
1.3
All electrical installation must be carried out by suitably qualified and competent personnel in accordance with all current statutory
requirements.
1.4
These instructions cover only the Elta Fans Ltd product and do not include the supply or installation of any safety equipment that may
be required e.g. adequate guarding or protection from rotating parts and proper electrical isolation.
1.5
Any declarations made by Elta Fans Ltd about product installation and safety, are dependant on the fan equipment being used within
installations which themselves meet the requirements of the relevant Standards and Directives of your region.
1.6
The fan is designed for use in an ambient temperature of -20°C up to +54°C and up to 95% relative humidity. EC fans are designed for
ambient temperatures up to +60°C. The fan is not suitable for corrosive or explosive atmospheres.
1.7
The installer should provide easy access to the fan to facilitate future maintenance.
1.8
The installer should ensure the fan is adequately supported.
1.9
This product is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the product by a person
responsible for their safety. Children should be supervised to ensure that they do not play with the product.
2.0
Installation
WARNING
– The fan must be isolated from the power supply during installation and maintenance. The fan must be earthed in
accordance with the local regulations.
2.1
Upon receipt, the fan equipment should be visually inspected to check for any damage. Ensure that the impeller is free to rotate.
2.2
If there are any queries concerning the fan equipment, Elta Fans Ltd should be contacted prior to the installation.
2.3
The fan must be securely mounted in the desired position to suit the application. The fan can be mounted at any angle.
2.4
Check the details on the motor rating plate to ensure that the correct power supply (voltage, frequency and phase) is available.
An incorrect power supply will lead to permanent damage to the fan motor.
2.5
Refer to the appropriate wiring diagram. Ensure that all earth connections are made.
2.6
Means for electrical disconnection must be incorporated in the wiring installation in accordance with the relevant wiring and electrical
regulations.
2.7
Precaution must be taken to locate the exhaust discharge terminal so as to avoid the backflow of gases into the room from the open
flue of gas or other fuel burning appliances.
3.0
Start Up
WARNING
– It is not good for any fan motor, for the user to use the power supply isolator to a fan as a means of day to day control.
This can reduce the life expectancy of the fan motor and may even lead to motor failure unlikely to be covered under our warranty. The
power supply isolator should only be used as a means of isolation of the power supply for maintenance and servicing requirements.
Day to day control should be provided to the user by means of one of the various type of control options as per the wiring diagrams
which follow in this document.
To help protect our fan motors, there is a delayed start function when the mains power is switched off at the isolator. A period of at
least 5 minutes should be allowed between power disconnection and reconnection. If the user is determined to switch the fan on and
off at the power supply isolator then the installer must advise the user of this motor protection function so that they wait the necessary
period of up to 5 minutes between switching on and off.
WARNING
– When switching off mains power for maintenance / servicing, High voltages are present at the terminals and within the
motor for up to 10 minutes after disconnection of the electrical supply.
3.1
Before power is supplied to the unit, check that the wiring is correct as per the fan connection diagram.
3.2
At initial start-up, check that impeller rotation and airflow direction is correct.
3.3
Check that the motor amperage draw does not exceed the nameplate rating.
EC fans only:
3.4
Minimum interval between consecutive starts: 5 minutes.
3.5
Maximum 1 connection from power supply cycle per 5 minutes.
AC