11
Elektroniksystem i Umeå AB Industrivägen 12, 90130 Umeå, Sweden
E-mail:
Web:
Pulse count (Pull down)
–
External pulse
Input signal between input and GND. Pulse signal from 3 to 12 voltage.
Select “Pulse input
(pull down)” in
the
application “Sensor Settings”. ELT input is
internally pulled down by ~50 k
Ω
*.
Pulse count (Pull up)
–
S0 input
S0 signal between input and ground.
Select “Pulse input
(pull up)” in
the
application “Sensor Settings”. ELT input is internally
pulled up by ~50 k
Ω
*.
www.ime.de