J48: 2½” – 6” Commissioning Instructions

 

IF THE REQUIRED OUTLET PRESSURE CAN NOT BE ACHIEVED WITH 
THE SPRING FITTED. 

1.

 

Choose a loading spring from the catalogue that will give the required outlet 
pressure range. 

For L.P. 65mm and 80mm units:   See Fig. 7. 

2.

 

Remove top cap. 

3.

 

Fully unscrew and remove the spring holder. 

4.

 

Remove loading spring. 

5.

 

Insert new loading spring. 

6.

 

Screw spring holder back in place ensuring that spigot is located in loading 
spring. 

7.

 

Adjust the outlet pressure, as described earlier, until the required setting is 
achieved. 

8.

 

Replace top cap. 

For H.P. 50mm and 80mm & L.P. 100mm and 150mm units:   See Fig. 8. 

9.

 

Remove top cap. 

10.

 

Slacken locknut on spring adjusting stem. 

11.

 

Turn spring adjuster anticlockwise to reduce loading on spring. 

12.

  Unscrew spring adjusting bush.

 

13.

 

Remove top spring holder and loading spring. 

14.

 

Insert new loading spring. 

15.

 

Place top spring holder over spring ensuring that spigot is located in loading 
spring. 

16.

 

Screw spring adjusting bush into top cover making sure that the end of the stem 
is located in the recess in the top spring holder. 

17.

 

Adjust the outlet pressure, as described earlier, until the required setting is 
achieved. 

18.

 

Tighten locknut. 

19.

 

Replace top cap. 

For H.P. 100mm and 150mm units:   See Fig. 9. 

20.

 

Remove top cap. 

21.

 

Turn spring adjusting nut anticlockwise to reduce loading on spring. 

22.

 

Remove 8 hexagon head screws that secure top cover to top diaphragm case. 
Carefully lift off top cover assembly and gasket. 

23.

 

Remove loading spring. 

24.

 

Install new loading spring over spring location washer in centre of diaphragm. 

25.

 

Replace gasket and top cover assembly and secure with 8 hexagon head 
screws. 

26.

 

Adjust the outlet pressure, as described on earlier, until the required setting is 
found. 

27.

 

Replace top cap. 

 

Fig. 6 

Fig. 7 

Fig. 9 

Fig. 8 