19
L-Bus
2 wire terminal with marking “Dat“ and “
┴
“
Terminals suitable for a cable with 2 wires of 2.5 mm²
Maximum voltage: 50 V DC
Primary or secondary addressing
Baud rate 300 or 2400 baud (automatic baud rate detection)
Protocol:
M-Bus
in combination with the external radio module IZAR RADIO EXTERN L-Bus RS232 the meter
sends the data every 3 minutes via the L-Bus module to the radio module
once the module is connected the meter recognizes that and disables the integrated radio
permanent! (as long as the L-Bus module is mounted)
the L-Bus module should be mounted on slot 2, to make sure that the same protocol will be
transferred as it is done via the integrated radio.
Fig. K
L-Bus module
4.4.2 Function
modules
Pulse input module
The two pulse inputs can be programmed independently of each other with values of 1, 2.5, 10,
25, 100, 250, 1000 or 2500 litres per pulse.
Possible units are all the energy units available in the meter, such as kWh/pulse and GJ/pulse,
but also volume units like l/pulse, m³/pulse or no units.
The input frequency is in the range 0 – 8 Hz, min. pulse duration 10 ms
Input resistance 2.2 M
Ω
Terminal voltage 3 V DC
Cable
length
≤
10 m
Pulse input 1 is marked “I1 -
┴
” on the module and “IN1” in the display, pulse input 2 “I2 -
┴
” on the
module and “IN2” in the display.
Fig. L
Pulse input module