PFA, BGT · Edition 03.11
21
6 Project planning information
6 .1 Installation
The BGT can be installed in any position.
Install in clean environment ensuring enclosure IP 54 or higher,
whereby no condensation is permitted.
It must be ensured that the module subrack is well ventilated,
in order to avoid overheating.
perforated plate
In the case of several module subracks mounted on top of one
another, we recommend removing the perforated plates from
between the module subracks, and inserting a rack-mounted
fan underneath the module subracks.
6 .2 Old-new PFA exchange
When exchanging the old PFA 700 (Order No. 8 439 510 0) for
the new PFA 700, the mains voltage on the new units must
be selected in accordance with the application requirements:
Old PFA 700
PFA 7
00
Run
Data
PROFIBUS
New PFA 700
Mains
voltage
Order No.
Mains
voltage
Order No.
110 – 240 V
AC
8 439 510 0
110/120 V AC
8 439 510 2
220/240 V
AC
8 439 510 1
A PROFIBUS plug connector with an internal additional EMC
protective circuit will be delivered with the new PFA 700 when
ordered as a replacement for the old PFA 700. If the new
PFA is operated in an old module subrack with the Order No.
8 440 228 3, this plug connector must be installed (see page
22 (Wiring) and page 23 (Accessories)).