Technical Data
8
enCore FC1
Operating Instructions
Page 75 of 78
8.3 Outputs
MFA8 output board
1 PhotoMos output (NC, max. 28.8 V, 120mA)
for alarm/message signaling.
3 PhotoMos outputs (NO, max. 28.8 V DC,
120mA) for alarm/message or pulse outputs of
up to 20 Hz.
4 analog outputs 0/4 - 20mA for
measurements.
Table 8: Outputs: Technical data
8.4 Interfaces for Digital Communication
CPU
TCP/IP interface (Ethernet 10/100MBit)
2 serial interfaces. Supported standards:
RS485 / RS422 / RS232.
MSER4
4 serial interfaces, electrically isolated.
Supported standards: RS485 / RS422 /
RS232.
MFE7
1 serial RS485 interface.
USB port
USB port for PC / laptop connection for
parameterization and service purposes.
Ethernet
communication
NTP, Modbus TCP, FTP, HTTP.
Serial communication
Modbus (ASCII, RTU), UNIFORM.
Table 9: Communication interfaces: Technical data