37
Parameter setting
Sensor Sewi KNX TH-L-Pr
• Version: 17.11.2016 • Technical changes and errors excepted.
At the end of the regulation, either "nothing" (status remains unchanged), an on or off
command (via the activated switching object) or a dim value can be sent.
Set, at which deviation from the setpoint value a
dim command is to be sent
. Spe-
cify the
dimming increment
and the
repetition cycle
for the dim command.
Define, up to which
response value
the dim actuator sends a brighter or darker com-
mand. On the one hand, this defines the range of use for the lamp, on the other hand,
once the minimum or maximum value has been reached, no unnecessary messages
are sent to the bus.
The light regulation can be
interrupted during switching or dimming
by response
objects, i.e. nothing else is transmitted via the dim-output. This results in the manual
light operation having priority.
Regulation starts on
• movement
• reception of a start/stop-object
• reception of a start/stop-object or
movement
Regulation stops on
• movement
• reception of a start/stop-object
• reception of a start/stop-object or
movement
Object evaluation
• 1 = start | 0 = stop
• 0 = start | 1 = stop
Object value prior to initial communication
0 • 1
Stop delay in seconds after the movement
has ended
0...1800; 120
Reaction to stop
• send nothing
• send off command
• send on command
• send value
Value in %
0...100
Send the dim command, if
• the actual value deviates from the set-
point value by more than X%
•the actual value deviates from the setpoint
value by more than X Lux
Target / actual difference in %
(for a deviation in %)
1...100; 20
Target / actual difference in Lux
(for a deviation in Lux)
1...2500; 100
Dimmer increments
100.00% • 50.00% • 25.00% • 12.5% • 6.25% •
3.13% • 1.56%
Repetition of the dim command in seconds
1...600; 6
Dim brighter with response value in %
1...100
Dim darker with response value in %
0...99