13
Setting of parameters
Pyranometer KNX PY
• Status: 22.07.2019 • Technical changes reserved. Errors reserved.
6.
Setting of parameters
6.1.
General settings
Measurement value in W/m²
• do not transmit
• transmit periodically
• transmit on change
• transmit on change and periodically
From measurement value change of
(only if sending “on change“ )
1 … 50%; 5 %
Periodically transmit measured value all
(only if sending “periodically“)
5 secs … 2 h
Use measurement value in kWh/m²
No • Yes
Transmission behaviour as with measured value in W/m²
Reset measurement value KWh/m² to 0
• at sunrise
• on reception of a communication object
Use maximum value
No • Yes
(Value is not retained after reset)
Use malfunction object
No • Yes
Maximum message rate
1 • 2 • 3 • 5 • 10 • 20 messages per second