![elsner elektronik 71160 Installation And Adjustment Download Page 7](http://html1.mh-extra.com/html/elsner-elektronik/71160/71160_installation-and-adjustment_2396652007.webp)
5
Installation and commissioning
KNX eTR 205/206 Light push button
• Version: 16.12.2020 • Technical changes and errors excepted.
1.1. Technical specifications
The product conforms with the provisions of EU guidelines.
1.1.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter
Installation position
) can be corrected in the ETS in order to ensure the specified
accuracy of the sensor (offset).
When
measuring temperature
, the self-heating of the device is compensated.
2.
Installation and commissioning
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
•
National legal regulations are to be followed.
Housing
plastic material, glass
Colours
similar to RAL 9003 signal white
Mounting
on-wall (directly or with a socket
Ø 60 mm, resp. cavity
wall socket for hole
Ø 68 mm)
Degree of protection
IP 10
Dimensions
housing approx. 81,5 x 81,5 (W x H, mm),
mounting depth approx. 12 mm
Total weight
approx. 70 g
Ambient temperature
Operation 0…+55°C, storage -30…+85°C
Ambient air humidity
5...95% RH, avoid bedewing
Operating voltage
KNX bus voltage
Bus current
max. 25 mA
Data output
KNX +/- bus terminals
Group addresses
max. 254
Allocations
max. 254
Communication objects
KNX eTR 205 Light: 92
KNX eTR 206 Light: 98
Temperature measurement
range
0…+55°C
Temperature resolution
0.1°C
Summary of Contents for 71160