elsner elektronik 71160 Installation And Adjustment Download Page 31

29

Setting the parameters

KNX eTR 205/206 Light push button

 • Version: 16.12.2020 • Technical changes and errors excepted

reached. You should set the time appropriate to the cooling system at this point (ob-
serve manufacturer's instructions).

Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.

In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.

PI control with predetermined application:

This setting provides fixed parameters for a cooling ceiling

Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.

2-point-control (only stage 2):

2-point-control is used for systems which are only set to ON or OFF.

Enter the hysteresis that prevents frequent on/off switching of temperatures in the
threshold range.

Maximum control variable is reached 
at setpoint/actual difference of (in °C)

1...5

Reset time (in min.)

1...255; 30

When blocked, the control variable should

• not be sent
• send a specific value

  Value (in %)
 

 (only if a value is sent)

0...100

Control type

• 

PI control

Setting of the controller by

• Controller parameter
• 

specified applications

  Application

• Cooling ceiling

Maximum control variable is reached 
at setpoint/actual difference of (in °C)

Cooling ceiling: 5

Reset time (in min.)

Cooling ceiling: 30

When blocked, the control variable should

• not be sent
• send a specific value

  Value (in %)
 

 (only if a value is sent)

0...100

Control type

is determined at a higher stage for com-
mon variables

• 

2-point-control

Hysteresis (in 0.1°C)

0...100; 20

Summary of Contents for 71160

Page 1: ...EN Installation and Adjustment KNX eTR Light Button for Temperature Control and Light KNX eTR 205 Light Item number 71160 KNX eTR 206 Light Item number 71170...

Page 2: ......

Page 3: ...evice 9 5 Display and operation at the device 10 5 1 Adjust room temperature using the example KNX eTR 205 Light 10 6 Maintenance and care 12 7 Disposal 12 8 Transmission protocol 13 8 1 List of all c...

Page 4: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Page 5: ...s 8 or 16 bit encoder or for scenario recall Temperature measurements Mixed value from own measured value and external values proportion can be set by percentage output of minimum and maximum values P...

Page 6: ...unction is enabled provided for 5 seconds See Fig 1 c and d This is extended for 5 seconds with each push of the button If the area function in the ETS is disabled the keys can be used normally at any...

Page 7: ...ooting should only be performed by an electrician CAUTION Live voltage There are unprotected live components inside the device National legal regulations are to be followed Housing plastic material gl...

Page 8: ...p tasks and only in the surroundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions 2 2 Inst...

Page 9: ...with 2 touch surfaces and temperature display 2 Light area with 2 touch surfaces 3 4 5 Fig 3 Back view with mounting 3 4 Screw holes for different sockets Fastening with 2 screws is sufficient For wa...

Page 10: ...ew the mounting onto the wall or socket The connecting wires bus line are led through the opening in the mounting Fig 4 Back view without mounting 5 KNX bus terminal for connection when mounted on a s...

Page 11: ...ice will enter an initialisation phase lasting a few seconds During this phase no information can be received or sent via the bus 4 Addressing the device The device is delivered ex works with the bus...

Page 12: ...isplay can be dimmed and switched off via the bus so that no value is displayed Option A Display of actual temperature room temperature The current room temperature is displayed It is not possible to...

Page 13: ...play jumps to the target temperature or to the basic setpoint shift depending on the presetting Changes with or are visible The display returns to the room temperature if no button is touched for 7 se...

Page 14: ...mode change e g Eco mode overnight or reset to the stored values The button functions can be disabled in the ETS or locked due to operating mode with priority 1 6 Maintenance and care Fingerprints on...

Page 15: ...Bytes 24 Temperature sensor measured value min max query Input WC 1 17 DPT_Trig ger 1 Bit 25 Temperature sensor measured value minimum Output R CT 9 1 DPT_Val ue_Temp 2 Bytes 26 Temperature sensor me...

Page 16: ...Bytes 55 Temp control Switch 0 Heating 1 Cooling Input WC 1 1 DPT_Switch 1 Bit 56 Temp control Setpoint Comfort heating Input Output RWCT 9 1 DPT_Val ue_Temp 2 Bytes 57 Temp control Setpoint Comfort...

Page 17: ...DPT_Switch 1 Bit 78 Temp control Comfort extension status Input Output RWCT 1 1 DPT_Switch 1 Bit 79 Temp control Comfort Extension time Input RWCT 7 5 DPT_Time PeriodSec 2 Bytes 80 Temp Controller Fan...

Page 18: ...PT_Bool 1 Bit 112 Logic input 6 Input WC 1 2 DPT_Bool 1 Bit 113 Logic input 7 Input WC 1 2 DPT_Bool 1 Bit 114 Logic input 8 Input WC 1 2 DPT_Bool 1 Bit 117 AND logic 1 1 bit switching output Output R...

Page 19: ...her a malfunction object is to be sent if the sensor is faulty Use Offsets to adjust the readings to be sent The unit can calculate a mixed value from its own reading and an external value Set the mix...

Page 20: ...cation program using parameters or de fine them via the bus using a communication object Threshold value setpoint using parameter Set the threshold values and hysteresis directly Threshold value setpo...

Page 21: ...valid until first Communication 300 800 200 Object value limit min in 0 1 C 300 800 Object value limit max in 0 1 C 300 800 Type of threshold value change Absolute value Increase decrease Interval upo...

Page 22: ...l the first call setting via objects is ignored For an adequate regulation of the indoor temperature comfort standby eco and build ing protection modes may be used Use switching output block No Yes As...

Page 23: ...standby mode and the two others are used to activate comfort mode or frost heat pro tection mode The comfort object then blocks the eco standby object and frost heat protection objects have the highes...

Page 24: ...other modes e g 2 C less for standby mode The grades for the setpoint changes is predefined Whether the change remains active only temporarily do not store or remains stored even after restoration of...

Page 25: ...mfort setpoint value is used as a basis If the comfort setpoint is used as the basis the increase decrease of this value is indi cated If the comfort setpoint is used as the basis a dead zone is deter...

Page 26: ...s are entered separately A starting setpoint value is defined as well as a temperature range in which the setpoint value may be changed Heating initial setpoint in 0 1 C valid until first Communicatio...

Page 27: ...only This is where you can decide whether to use a common variable for heating and cooling If the 2nd stage has a common variable this is also where you determine the control mode of the 2nd stage Wh...

Page 28: ...esponds to deviations from the set point In case of a short reset time the control responds with a fast increase of the con trol variable In case of a long reset time the control responds somewhat les...

Page 29: ...ntrol only stage 2 2 point control is used for systems which are only set to ON or OFF Enter the hysteresis that prevents frequent on off switching of temperatures in the threshold range Control type...

Page 30: ...ot the second stage is then added PI controller with control parameters This setting allows individual input of the parameters for PI control Specify the deviation from the setpoint value which reache...

Page 31: ...ol only stage 2 2 point control is used for systems which are only set to ON or OFF Enter the hysteresis that prevents frequent on off switching of temperatures in the threshold range Maximum control...

Page 32: ...ing Select which actuating variable s are to control the output The selection depends on the type of heating cooling control and the settings made for the actuating variables Select whether the first...

Page 33: ...nt lighting All LEDs individually controllable LED mode All LEDs as ambient lighting Brightness 0 100 30 Use objects No Yes Object value on off after reset if objects are used 0 1 Use automatic switch...

Page 34: ...dimming and whether the dimming command is to be repeated LEDs for temperature display display actual value only display only target value base shift display actual value and target value base shift U...

Page 35: ...cts Determine what the out put should send if logic 1 and 0 If the output type is a 1 bit object set the output values for the various conditions Repeat the dim command on long button press every 0 1...

Page 36: ...60 63 1 Output value object A if logic 0 0 255 100 360 63 0 Output value object B if logic 0 0 255 100 360 63 0 Output value object A If block active 0 255 100 360 63 0 Output value object B If block...

Page 37: ...e following inputs are available for the OR logic Switching output AND logic 1 Switching output AND logic 1 inverted Switching output AND logic 2 Switching output AND logic 2 inverted Use block No Yes...

Page 38: ...bH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de Technical support 49...

Reviews: