Setting the parameters
KNX eTR 205/206 Light push button
• Version: 16.12.2020 • Technical changes and errors excepted
Block
If necessary, activate the block for the logic output and set what a 1 or 0 at the block
input means and what happens in the event of a block.
Monitoring
If necessary, activate the input monitoring. Set which inputs are to be monitored, at
which intervals the inputs are to be monitored and what value the "monitoring status"
should have, if the monitoring period is exceeded without a feedback being given.
9.8.2. OR LOGIC connection inputs
The OR logic connection inputs are the same as those for the AND logic. Additionally,
the following inputs are available for the OR logic:
Switching output AND logic 1
Switching output AND logic 1 inverted
Switching output AND logic 2
Switching output AND logic 2 inverted
Use block
No • Yes
Assessment of the block object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first Commu-
nication
0 • 1
Output behaviour
when blocking
• Do not send message
• Send block value [see above,
output value if block active]
when released
(with 2 second release delay)
• Do not send message
• transmit value for current logic status
Use input monitoring
No • Yes
Input monitoring
• 1 • 2 • 3 • 4
• 1 + 2 • 1 + 3 • 1 + 4 • 2 + 3 • 2 + 4 • 3 + 4
• 1 + 2 + 3 • 1 + 2 + 4 • 1 + 3 + 4 • 2 + 3 + 4
• 1 + 2 + 3 + 4
Monitoring period
5 s • ... • 2 h; 1 min
Output behaviour on exceeding the moni-
toring time
• Do not send message
• Send value exceeding [= value of the
parameter "Monitoring period"]