background image

2

Description

Indoor sensor KNX TH-B-UP

 • Software version 3.1 and higher

Version: 22.02.2017 • Technical changes and errors excepted.

1.

Description

The 

Indoor sensor KNX TH-B-UP

 measures the temperature and air humidity and

calculates the dew point. Via the bus, the sensor receives external measuring values
and processes them to an overall temperature and air humidity value (composite
results) together with its own data. The 

KNX TH-B-UP

 features two buttons that may

be used to modify the room temperature (nominal temperature), to switch between the
operating modes or as freely programmable bus buttons.

The 

KNX TH-B-UP

 provides six switched outputs with adjustable threshold values as

well as additional AND and OR logic links. The sensor features a PI control for heating
and cooling (depending on the temperature) as well as ventilation (depending on the
air humidity) and can output a warning to the bus as soon as the comfort field (as per
DIN 1946) is exited.

The integrated display shows own values as well as data received via the bus 
(e.g. date, time of day). The housing is supplemented with a frame of the switch series
used in buildings, and thus fits seamlessly into the interior fittings.

Functions:

Measuring the 

temperature

 and 

air humidity

 (relative and absolute), 

calculation of the 

dew point

 

Composite values

 from own measured values and external values 

(proportions are adjusted as a percentage) 

Display

 1-3 lines (own values or values received via bus)

2 buttons

. Configuration as a bus button or to modify the nominal 

temperature and to switch between the operation modes (see also  

Change 

ambient temperature with the buttons

, Page 8)

PI-controller for heating

 (one or two-stage) and 

cooling

 (one or two-stage) 

according to temperature. Regulation according to separate setpoints or basic 
setpoint temperature

PI controller for humidity

 according to humidity: Dehumidifying/

humidifying (single level) or dehumidifying (single or double level) 

6 Threshold values

 can be adjusted per parameter or via communication 

objects 

8 AND and 8 OR logic gates

, each with 4 inputs. All switching events as well 

as 16 logic inputs (in the form of communications objects) are used as inputs 
for the logic gates. The output from each gate can be configured optionally as 
1-bit or 2 x 8-bit

Configuration is made using the KNX software ETS. The 

product file

 can be

downloaded from the Elsner Elektronik website on 

www.elsner-elektronik.de

 in the

“Service” menu.

1.1. Deliverables

Housing with display

Baseplate

Summary of Contents for 70370

Page 1: ...nium 70375 anthracite EN Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elektronik de Germany Fax 49 0 70 33 30 945 20 www elsner elektronik de KNX TH B UP Thermal hygrometer Technical Service 49 0 70 33 30 945 250 ...

Page 2: ...nd thus fits seamlessly into the interior fittings Functions Measuring the temperature and air humidity relative and absolute calculation of the dew point Composite values from own measured values and external values proportions are adjusted as a percentage Display 1 3 lines own values or values received via bus 2 buttons Configuration as a bus button or to modify the nominal temperature and to sw...

Page 3: ...ting in junction box Ø 60 mm 42 mm depth Protection category IP 20 Dimensions Housing approx 55 x 55 W x H mm installation depth approx 15 mm Baseplate approx 71 x 71 W x H mm Total weight approx 50 g Ambient temperature Operation 0 50 C storage 10 60 C Ambient humidity max 95 RH avoid condensation Operating voltage KNX bus voltage Bus current max 6 mA max 10 mA when programming LED active Data ou...

Page 4: ...onents inside the device National legal regulations are to be followed Ensure that all lines to be assembled are free of voltage and take precautions against accidental switching on Do not use the device if it is damaged Take the device or system out of service and secure it against unintentional use if it can be assumed that risk free operation is no longer guaranteed The device is only to be use...

Page 5: ... ducts which lead from other rooms to the junction box in which the sensor is mounted Warming or cooling of the building structure on which the sensor is mounted e g due to sunlight heating or cold water pipes Connection lines which lead from warmer or colder areas to the sensor Temperature variations from such sources of interference must be corrected in the ETS in order to ensure the specified a...

Page 6: ...cs You must not exceed a relative humidity of 95 Avoid condensation After the bus voltage has been applied the device will enter an initialisation phase lasting a few seconds During this phase no information can be received or sent via the bus 3 Display and operation at the device Specifications for the display are set in the ETS and the use of the push buttons is permitted or disabled Basically t...

Page 7: ...e reads Base target value reduced Fig 5 Mode display with scale display and number Shows the set target value change The control position in the image reads Base target value reduced to 1 0 Fig 6 Mode display with scale display and range Shows the possible adjustment range as set in the ETS The control position in the image reads Base target value reduced Fig 7 Mode display with scale display rang...

Page 8: ...e individual operating modes can also be locked for manual selection in the ETS Comfort mode Comfort present target temperature will be used Standby mode Standby absent during day target temperature will be used Eco mode Night target temperature will be used Building protection mode Building protection target temperature will be used The symbol will blink when the mode has been activated but the a...

Page 9: ...an 2 secs Changes between the operating modes Comfort Standby Eco and Building Protection if deblocked in the ETS Extend Comfort mode in Eco mode press both buttons at the same time longer than 2 secs Switches from Eco to Comfort mode again for a certain time e g if the rooms are used longer in the evening The period is defined in the ETS up to 10 hours The time remaining in Comfort mode is displa...

Reviews: