B. Outdoor temperature block
After the setting of the indoor temperature, now select the maximum outdoor
temperature up to which the window shall remain closed.
The outdoor temperature block keeps the window closed as long as the temperature is
below the selected value. This means that in automatic mode, an opened window is
closed and not opened again if the indoor temperature value (chapter A) is exceeded.
Thus avoids energy losses during ventilation and protects plants from cold external air.
ATTENTION!
The outdoor temperature block should be set to a temperature
above
0°C, if possible. If a window is opened while temperatures
are
below
0°C, frozen rubber seals can get damaged.
The hysteresis of the outdoor temperature block is 2°C. That means, the window
ventialtion is released only after the outdoor temperature has extended the set value
more than 2°C.
The presetting for the outdoor temperature block is 5°C.
Adjust the value with (higher) and (lower) or select
(off) in order to switch off
the outdoor temperature block. You reach the setting
by pressing once more
when the display shows “-20°C”.
Press
in order to access the setting of the next parameter.