Technical Manual TAR x810-2 Cold Storage Controllers

  Installation / Run-Up

Applications with Airflow Defrost

If this defrost method is used, there is no need for mounting a 

defrost sensor at the evaporator. In this case the sensor can 

be disabled. If the correction parameter 

P20

 is set to -10,1, 

the display shows "oFF" and the sensor is disabled. Correcting the 

parameter upward enables the sensor again. 

The controller then terminates a defrost cycle only by time which is 

set by parameter

 P28

.

Upon applying voltage to the controller the display shows the tem-

perature  of  the  control  (room)  sensor. After  you  have  entered  the 

access code (see chapter "unlock keys") you have to program the 

configuration of the controller to suit your application:

• 

kind of temperature sensor and display value  (°C/°F)

• 

Please note that you need the special access code '70' to  

 

 

change sensors. Please note that all temperature setpoints will  

 

be set to default.

• 

switching mode of relay K1: parameter P10 

• 

defrost method: P23

• 

evaporator fan mode: P13

• 

alarm mode: P30

The basic setup is now complete and you can edit the missing set-

points, delay times etc.

Sensor correction

If for any reason the actual sensor values displayed should not match 

with the temperature you read from a high accuracy thermometer, you 

can correct the error with parameters

 P19/P20.

org. created: 4.3.09, tkd/jr 

checked: 8.4.2009, ek/ha 

 

released:  27.4.2009, mkt/sha  

translated:  11.5.09, tkd/jr

 CONNECTION INFORMATION & SAFETY INSTRUCTIONS

The guarantee will lapse in case of damage caused by failure 

to comply with these operating instructions! We shall not be 

liable for any consequent loss! We do not accept liability for 

personal injury or damage to property caused by inadequate 

handling or non-observance of the safety instructions! The 

guarantee will lapse in such cases. 

   

This manual contains additional safety instructions in the  

   

functional description. Please note them!

If you notice any damage, the product may not be connected 

to mains voltage! Danger of Life!

A riskless operation is impossible if:

• The device has visible damages or doesn't work

• After a long-time storage under unfavourable conditions

• The device is strongly draggled or wet

• After inadequate shipping conditions
• Never use this product in equipment or systems that are  

  intended to be used under such circumstances that may  

  affect human life. For applications requiring extremely  

  high reliability, please contact the manufacturer first.

• 

The product may only be used for the applications  

  described on page 1.
•  Electrical installation and putting into service must be  

  done from qualified personnel. 

• 

 During installation and wiring never work when the 

  electricity is not cut-off ! Danger of electric shock!

• 

 Never operate unit without housing. 

  Danger of electric shock!

•  

All ‘PE’ terminals must be connected to ground.  

  Danger of electric shock! 

Additionally, the internal noise  

  filter will not work, faulty indicated values may occur.

•  Please note the safety instructions and standards of your  

  place of installation!
•  Before installation: Check the limits of the controller and  

  the application (see tech. data). Check amongst others:

  - Make sure that all wiring has been made in accordance  

    with the wiring diagram in this manual.

  - Supply voltage (is printed on the type label).

  - Environmental limits for temperature/humidity. 

  -  Maximum admitted current rate for the relays. Compare  

    it with the peak start-up currents of the controlled loads 

    (motors, heaters,etc.). 

 

  Outside these limits malfunction or damages may occur.
•  Sensor/probe cables must be shielded. Don’t install them  

  in parallel to high-current cables. Shielding must be  

  connected to PE at the end close to the controller. 

  If not, inductive interferences may occur. 
•  Please note for elongation: The wire gauge is not critical,  

  but should have 0,5mm² as a minimum.
•  Mounting the controller close to power relays is    

  unfavourable. Strong electro-magnetic interference,  

  malfunction may occur!
•  Take care that the wiring of interface lines meets the  

  necessary requirements.
• All used temperature sensors must be identical. Never  

  use different types at the same time. This will not work.
•  TF-type sensors are not designed for being immersed in  

  fluids permanently. In such a case, always use dip-fittings.  

  With extreme temperature variations, the sensor may be  

  damaged.

Cleaning

 

The  use  of  a  dry,  lint-free  cloth  and  household  agents  is 

sufficient to clean the product. 

Never use acids or acidic fluids!  Risk of damage!

Summary of Contents for TAR 1810-2

Page 1: ...ingle differences Changed terminal assignment Be careful while replacing older types Error messages now shown as codes and displayed as listing at P52 Unlock Acess code entry now possible at each para...

Page 2: ......

Page 3: ...g function is locked automatically Manual Defrost While the actual value is visible Press key for more than 2 seconds Defrost ON Press key for more than 2 seconds Defrost OFF Start up behavior Directl...

Page 4: ...frigeration P11 88 Refrigeration Compressor Idle Time 0 59 minutes 2 minutes P12 88 Fan stop go temperature 100 C 100 C Hyst 3K fixed 50 C P13 88 Fan mode 1 2 3 4 see text 1 P14 88 Fan delay after def...

Page 5: ...four times available P24 P27 B by digital input DI1 see chapter digital input In this case P35 will take effect as a defrost OFF time C manually P49 The defrost device is always driven from the n o co...

Page 6: ...als 11 12 Never connect mains voltage to these terminals danger of destruction This external contact must be suitable for 5VDC 1mA Because all units are connected parallel on the data bus every unit h...

Page 7: ...0 11 8 9 K 4 K 3 K 2 DO GND NDO 3 4 5 6 2 L N PE 1 21 K 1 20 17 18 19 F2 16 F1 97 3 81 Made in Germany ELREHA 8 35 1 38 59 2 32 26 1 02 39 1 54 For all described products there is a declaration of con...

Page 8: ...age under unfavourable conditions The device is strongly draggled or wet After inadequate shipping conditions Never use this product in equipment or systems that are intended to be used under such cir...

Reviews: