 Functional Description

Display & Sensors

The  controller  is  able  to  work  with  temperature 

sensors of the TF 201 or TF 501 (Pt1000) series, 

set by 

P21.

 

Ranges

:

  P21 = 1 (TF 201).................... -50...+100°C

  P21 = 3 (TF 501/Pt1000)....... -100...+300°C

  Please note the specific temperature restric- 

  tions of the used sensors (e.g. -40...+80°C of  

  the standard-TF-types) and ask for matching  

  types if necessary.  

Sensor 2 (evaporator sensor) can be disabled.

 

Temperature Control

The actual temperature from the control sensor (

P01

is compared with the control setpoint 

(P03).

 Depen-

ding on the result, the cooling relay switches power 

relays of compressors or solenoid valves. A switching 

hysteresis (

P09

) prevents from short cycling, an idle 

time (

P11

) prevents a compressor from switching 

ON again immediately. In order to be fail-safe in case 

of any internal power failure, there is a possibility of 

selecting the correct switching mode (

P10

). In refri-

geration mode the N/O relay contacts are used so 

that the load is shut off in case of failure. In freezing 

mode the load is connected to the N/C contact, with 

the load running constantly in case of failure.
Setpoint range

With parameters 

P07/P08

 you can limit the setpoint 

range.
Switching mode of relay K1

The switching characteristic of relay K1 (= cooling 

mode) is defined by parameter 

P10 

(as explained 

above). 

1

=  refrigeration 

  Load is switched by the N/O contact,    

  If actual value = P03+P09 : Relay K1 activated

2

= freezing 

  Load is switched by the N/C contact,

  If actual value = P03+P09 : Rel. K1 de-activated 

3

= Heating 

  If actual value = P03-P09 : Rel. K1 is now a  

  heating relay and will be activated

2. Setpoint / day-night-shift

To economize energy, e.g. at night, the unit is able 

to work with a 2nd setpoint (

P04

). This setpoint can 

be activated by the internal time-switch (

P05/P06

) or 

the digital input DI1. The decimal point of the display 

flashes while the 2nd setpoint is present.

Temperature alarm

An alarm relay (K4) and a built-in buzzer are available 

for warning purposes. If the temperature measured 

by  the  control  sensor  exceeds  the  range  set  by 

P32/P33

, then the display flashes and a time delay 

(

P31

) starts. After this timer is run down, the alarm 

relay and the buzzer will be activated. 

P32

 is relative 

to  setpoint 

P03

,  so 

P32

  will  be  shifted  the  same 

amount as the setpoint. 

-- Any keypress resets the buzzer. --

If the temperature has left the range, 

P18

 shows the 

remaining time until an alarm occurs.

If the temperature comes back to the working range, 

relay and buzzer will be reset automatically.

Alarm relay operation modes

With parameter 

P30

 you select the mode of alarm 

relay and internal buzzer:

 

0

= Alarm relay active ON

1

= Alarm relay active OFF

2

= Alarm relay active ON, buzzer de-activated

3

= Alarm relay active OFF, buzzer de-activated

4

= Alarm relay works like the built-in buzzer, to  

  connect an external horn

5

= Continuous ON of relay K4 if control setpoint 2  

  is being activated. Alarm messages will be  

  forwarded by buzzer/alarm-LED only. With this  

  function, light can be switched by time control. 

6

= Alarm relay can be switched via data interface  

  only. This works as well as the controller is de- 

  activated by interface or digital input. The swit- 

  ching command keeps stored, so the relay  

  position will be restored after a breakdown of  

  supply voltage.
Additionally, the alarm function can be started by 

interrupting the digital input DI1 (see 

P34

).

Real time clock

The 

TAR

 Cold Storage Controller contains a real time 

clock which allows you to initiate four (8 with AZV) 

defrost cycles a day. The timer has a power backup 

for about 10 days in case of power failure. 

The time of the day and the date can be set with 

parameters 

P41

...

P45

The defrost times are set with 

P24

...

P27

 in 10 minute 

increments in a 24 hour (military) format. Example: 

13.20 = 01:20 p.m.

The second setpoint switch is made with 

P05/P06

.

Because the display has only three digits, the time 

value comes in the following format: 

Switch  times  can  be  de-activated  by  setting  to 

'

oFF

'.

While the data recording function is active, time and 

date cannot be adjusted. 

To  adjust  the  clock,  first  de-activate  data  logger 

(

P39

=0).

Defrost

One relay output is used to control a defrost de-

vice. 
Defrost Initiation

A.  by internal timer, four times available 

 

(

P24

...

P27

)

B.  by digital input DI1 (see chapter 'digital input'). 

 

In this case P35 will take effect as a 'defrost  

 

OFF' time.

C.  manually (

P49

). 

The  defrost  device  is  always  driven  from  the  n/o 

contact of relay K2. There is no need for external 

interlocking the defrost output with the cooling output 

since the temperature controller is disabled while a 

defrost cycle. With 

P23

 you can select four different 

defrost modes.

Parameter 

P15

  shows  the  remaining  time  of  the 

momentary defrost cycle until termination by time.

Defrost Modes 

With 

P23

 a defrost mode can be set, which works in-

dependent from the behaviour of the control relay.

1 =

  Heater or Free Air Defrost 

 

If a defrost cycle starts, the defrost relay is  

 

energized (= heater ON) and K1 terminates  

 

cooling. (relay de-activated if P10=1, activated  

 

if P10=2 )

2 = 

Hot Gas Defrost 

 

If a defrost cycle starts, the defrost relay is  

 

energized (bypass-valve open) and also K1  

 

(solenoid valve open/relay activated if P10=1,  

 

de-activated if P10=2 ). 

3 =

  like 1, but with additional 

 

defrost time doubling (

AZV

)

4 = 

like 2, but with additional 

 

defrost time doubling (

AZV

Defrost time doubling 

(AZV)

This is a simple function to double the quantity of the 

potential defrost cycles (4 --> 8). The unit generates 

new defrost times automatically by adding 12 hours 

to existing times.

Example:

If a defrost cycle is fixed at 14:30, the unit starts 

an  additional  cycle  at  2:30  (am)  without  entering 

this time.

3rd Position=

minutes x 10

1st and 2nd

Position=

hours

Manual Defrost Initiation

A.

  At parameter 

P49

 with key "

"

B.

  While the display shows the actual 

 

temperature by holding the "

" key (> 2,5 sec.)

Defrost Termination

A defrost cycle can be terminated as follows : 

A

:  Thermal termination. 

 

Whenever the evaporator sensor temperature  

 

(

P02

) exceeds the temperature limit set with

 

parameter 

P22

, defrosting will be terminated.  

 

If not necessary, switch off the evaporator  

 

sensor at 

P20

.

B

:   Termination by (safety) time.

 

The time set by parameter

 P28

 is the 

 

maximum time a defrost cycle can last before  

 

it is terminated automatically. 

C

:   Manual termination.

 

With parameter 

P49

 you can terminate a 

 

defrost cycle by pressing the "

" key. 

 

While the actual temperature (

P01

) is on the  

 

display, a defrost cycle can be terminated by  

 

holding the "

" key (> 2,5 sec.)

D. 

If the defrost limit sensor fails, the defrost cycle  

 

will be stopped immediately. 

   

After the defrost cycle is terminated, the beginning of 

the cooling function is delayed (

P29

). This prevents 

freezing water drops on the evaporators surface. 

P16

 shows the remaining time until cooling starts 

again. 

(DH) Display Hold Function

This function allows to hold the last measured actual 

temperature value on the display during a defrost 

cycle. After the defrost cycle has been terminated, 

the display shows the current measured value again. 

The DH-function can be initiated by 

P50

.

Evaporator Fan Control

Four different modes of fan operation can be selected 

with parameter 

P13

A temporal fan-ON delay is active after a defrost 

cycle (

P14

).

A thermostatic delay is always active. That means 

the fan starts only if the temperature measured with 

the evaporator sensor is 3K below the fan stop/go 

temperature (

P12

). If this function is not desired, 

P12 

can be set to its upper border to make it inefficient.

While  the  drain  time  (

P29

)  the  fan  remains  stop-

ped.

Fan  Modes (P13)

1 = 

Fan runs if compressor output (K1) is on.

 

 

After defrosting the fan output is OFF until the  

 

programmed Fan Delay Time (

P14

) is 

 

complete.  

 

.

2 =  

Fan runs continously, except during defrost  

 

and Fan Delay Time (

P14

) after defrost. 

 

Thermostatic fan delay: The fan stops if the  

 

temperature measured with the evaporator  

 

sensor exceeds (

P12

). If this function is  

 

not desired, 

P12 

can be set to its upper border  

 

to make it inefficient.

3 = 

Fan runs if the compressor output (K1) is on,  

 

and during defrost

.  

 

 

The temporal fan delay must be set to "0".  

 

This mode can be used for free air defrost. 

4 = 

Fan runs permanently, except if unit is 

 

switched off via interface.

(

P17

) informs about the remaining time until the fan 

starts again.

Special case

If digital input DI1 is used for door monitoring, the fan 

will stop immediately if the door opens.

Practical conditions

The fan is always switched by the n/o contact of 

relay K3.
If you want to realize a thermostatic delay, select fan 

mode 

2

 and adjust setpoint 

P12

.

If you want to realize a thermostatic delay and free 

air defrost, please realize a parallel connection of fan 

relay and defrost relay.

Summary of Contents for TAR 1810-2

Page 1: ...ingle differences Changed terminal assignment Be careful while replacing older types Error messages now shown as codes and displayed as listing at P52 Unlock Acess code entry now possible at each para...

Page 2: ......

Page 3: ...g function is locked automatically Manual Defrost While the actual value is visible Press key for more than 2 seconds Defrost ON Press key for more than 2 seconds Defrost OFF Start up behavior Directl...

Page 4: ...frigeration P11 88 Refrigeration Compressor Idle Time 0 59 minutes 2 minutes P12 88 Fan stop go temperature 100 C 100 C Hyst 3K fixed 50 C P13 88 Fan mode 1 2 3 4 see text 1 P14 88 Fan delay after def...

Page 5: ...four times available P24 P27 B by digital input DI1 see chapter digital input In this case P35 will take effect as a defrost OFF time C manually P49 The defrost device is always driven from the n o co...

Page 6: ...als 11 12 Never connect mains voltage to these terminals danger of destruction This external contact must be suitable for 5VDC 1mA Because all units are connected parallel on the data bus every unit h...

Page 7: ...0 11 8 9 K 4 K 3 K 2 DO GND NDO 3 4 5 6 2 L N PE 1 21 K 1 20 17 18 19 F2 16 F1 97 3 81 Made in Germany ELREHA 8 35 1 38 59 2 32 26 1 02 39 1 54 For all described products there is a declaration of con...

Page 8: ...age under unfavourable conditions The device is strongly draggled or wet After inadequate shipping conditions Never use this product in equipment or systems that are intended to be used under such cir...

Reviews: