TAA 2140, TAA 22140
Parameters
No.
Parameter
Range
Factory set
P01
.... Actual value signal input 1 ..................... -50...300 .................................................................................................................display only
P02
.... Actual value signal input 2 ..................... -50...300 .................................................................................................................display only
P03
.... Display Mode ......................................... 0= without decimal place, with noise filter ..............................................................2
1= with decimal place and noise filter
2= with decimal place, without noise filter
P04
.... Alternating Mode .................................... 0= not alternating ...................................................................................................0
1= every 16 seconds the display changes from P01 to P02.
In doing so,
the parameter number appears always for a short time
P05
.... Display with 10V at signal input 1 ......... -50...300 .................................................................................................................100
P06
.... Display with 0V at signal input 1 ............ -50...300 .................................................................................................................-50
P07
.... Display with 20mA at signal input 2 ....... -50...300 .................................................................................................................100
P08
.... Display with 4mA at signal input 2 ......... -50...300 .................................................................................................................0
P09
.... Correction value for signal input 1 ......... ± 10.0 .....................................................................................................................0
P10
.... Correction value for signal input 2 ......... -10,1...+10.0 (With -10.1, this input is switched off, P02 changes to "oFF") ..........0
P11
.... Alarm upper limit signal of input 1 .......... -50...+300°C ...........................................................................................................+300
P12
.... Alarm lower limit signal of input 1 .......... -50...P07 ................................................................................................................-50
P13
.... Alarm upper limit signal of input 2 .......... -50...+300°C ...........................................................................................................+300
P14
.... Alarm lower limit signal of input 2 .......... -50...P09 ................................................................................................................-50
P15
.... Alarm delay ............................................ 1...99 minutes ........................................................................................................60 minutes
P16
.... Alarm repetition time .............................. 0...99 minutes (0 = no alarm repetition after a reset) .............................................15 minutes
P17
.... Remaining time Alarm/Reset .................................................................................................................................................display only
P18
.... Access Code .......................................... 88 ...........................................................................................................................00
Liste des paramètres
Nr.
Paramètre
Plage
Val. usine
P01
.... Mesure entrée 1 ..................................... -50...300 .................................................................................................................--
P02
.... Mesure entrée 2 ..................................... -50...300 .................................................................................................................--
P03
.... Mode d'affichage .................................... 0= sans 0.1 avec filtrage ........................................................................................2
1= avec 0.1 avec filtrage
2= avec 0.1 sans filtrage
P04
.... Mode display .......................................... 0= Affichage normal ...............................................................................................0
1= toutes les 16 secondes, l'afficheur permute entre P01 et P02, pour
visualiser 2 mesures en même temps
P05
.... Affichage entrée 1 pour 10V .................. -50...300 .................................................................................................................100
P06
.... Affichage entrée 1 pour 0V .................... -50...300 .................................................................................................................-50
P07
.... Affichage entrée 2 pour 20mA ............... -50...300 .................................................................................................................100
P08
.... Affichage entrée 2 pour 4mA ................. -50...300 .................................................................................................................0
P09
.... Correction mesure entrée 1 ................... ± 10.0 .....................................................................................................................0
P10
.... Correction mesure entrée 2 ................... -10,1...+10.0 (en réglant jusqu'à -10.1, l'afficheur ..................................................0
indique "oFF" et l'entrée est inhibée)
P11
.... Seuil haut alarme entrée 1 ..................... -50...+300°C ...........................................................................................................+300
P12
.... Seuil bas alarme entrée 1 ...................... -50...P07 ................................................................................................................-50
P13
.... Seuil haut alarme entrée 2 ..................... -50...+300°C ...........................................................................................................+300
P14
.... Seuil bas alarme entrée 2 ...................... -50...P09 ................................................................................................................-50
P15
.... Retard d'alarme ..................................... 1...99 minutes ........................................................................................................60 minutes
P16
.... Temps avant répétition alarme ............... 0...99 minutes (0=pas de répétition alarme après acquittement) ...........................15 minutes
P17
.... Temps restant avant alarme .................. affichage seul.
P18
.... Entrée code de déverrouillage ............... 88 ...........................................................................................................................00
We state the following: When operated in accordance with the technical manual, the criteria have been met that are outlined in the guidelines of the
council for alignment of statutory orders of the member states on EMC-Directive (2004/108/EC) and the Low Voltage Directive (LVD 2006/95/EC).
This declarations are valid for those products covered by the technical manual which itself is part of the declaration. To meet the requirements, the
currently valid versions of the relevant standards have been used
This statement is made from the manufacturer / importer
by:
ELREHA Elektronische Regelungen GmbH
Werner Roemer, Technischer Leiter,
Technical Director
D-68766 Hockenheim
www.elreha.de
Hockenheim
.............
15.04.2009
.......................................................
(Name / Anschrift /
name / adress
)
Ort/
city
Datum/
date
Unterschrift/
sign
EG-Statement of Conformity
Parameterliste
Nr.
Parameter
Bereich
Werkseinst.
P01
.... Istwert 0-10V-Eingang (F1) .................... -50...300 .................................................................................................................nur Anzeige
P02
.... Istwert 4-20mA-Eingang (F2) ................. -50...300 .................................................................................................................nur Anzeige
P03
.... Anzeigemodus ....................................... 0= ohne Nachkommastelle mit Störungsfilter ........................................................2
1= mit Nachkommastelle und Störungsfilter
2= mit Nachkommastelle ohne Störungsfilter
P04
.... Display Modus ....................................... 0= normale Anzeige ...............................................................................................0
1= alle 16 Sekunden wird von P01-Anzeige auf P02-Anzeige gewechselt.
Dazu wird jeweils kurz die Parameternummer eingeblendet.
P05
.... Anzeige bei 10V an Signaleingang 1 ..... -50...300 .................................................................................................................100
P06
.... Anzeige bei 0V an Signaleingang 1 ....... -50...300 .................................................................................................................-50
P07
.... Anzeige bei 20mA an Sign.eingang 2 .... -50...300 .................................................................................................................100
P08
.... Anzeige bei 4mA an Sign.eingang 2 ...... -50...300 .................................................................................................................0
P09
.... Korrekturwert Eingang F1 ...................... ± 10.0 .....................................................................................................................0
P10
.... Korrekturwert Eingang F2 ...................... -10,1...+10.0 (Mit -10.1 ist dieser Fühler abgeschaltet, Anzeige wechselt ............0
dann auf "oFF")
P11
.... Alarm-Obergrenze Eingang F1 .............. -50...+300°C ...........................................................................................................+300
P12
.... Alarm-Untergrenze Eingang F1 ............. -50...P07 ................................................................................................................-50
P13
.... Alarm-Obergrenze Eingang F2 .............. -50...+300°C ...........................................................................................................+300
P14
.... Alarm-Untergrenze Eingang F2 ............. -50...P09 ................................................................................................................-50
P15
.... Alarmverzögerung ................................. 1...99 Minuten ........................................................................................................60 Minuten
P16
.... Alarmquittierungszeit ............................. 0...99 Minuten (0=keine Alarmwiederholung nach Quittierung) .............................15 Minuten
P17
.... Restlaufzeit Alarm/Quittierung ...............................................................................................................................................Nur Anzeige
P18
.... Zugangscode ......................................... 88 ...........................................................................................................................00
original set up: 14.4.09, tkd/jr
checked: 15.4.09, ek/ha
approved: 15.4.09, mkt/sha
transl.(E):
korr: 3.9.15, tkd/jr