Betriebsanleitung

 5311554-00/02

ge

/01 

    

            2018-05-30 tkd/jr

Kältemittel-Leckwarner 

Refrigerant Leak Detector

EGS AE

ELEKTRONISCHE  REGELUNGEN  GMBH

Vor Inbetriebnahme diese Betriebsanleitung sorgfältig lesen! Entstehen durch Nichtbeachtung 

Schäden, erlöschen die Garantieansprüche. Diese Dokumentation würde mit größter Sorgfalt erstellt. 

Dennoch können wir für die vollständige Richtigkeit keine Garantie übernehmen.
Please read these instructions carefully before applying power. Your attention is drawn to the

fact that the warranty is subject to the application of power sources that are within the limits

specified in this manual. Repairs or modifications made by anyone other than ELREHA will also

void the product warranty. This documentation was compiled with utmost care, however, we

cannot guarantee for its correctnesss in every respect.

ELREHA GmbH

D-68766 Hockenheim, Germany, 

Schwetzinger Str. 103

Telefon (+49)(0) 6205/2009-0  -  Fax (+49)(0) 6205/2009-39  -  [email protected]

 

Bitte Sicherheits- und 

 

Betriebshinweise beachten! 

 

Please note Safety and 

 

Operating Instructions !

Funktionen 

Sensoranschluss

Es können externe Sensoren mit einem 4-20mA Ausgangssignal verwendet 

werden.
Alarmgrenzen 

Alarmgrenzen können mit DIP-Schaltern festgelegt werden (siehe Anschluss-

bild).
Anzeige im Normalzustand

Im Normalzustand zeigt die EGS Auswerteinheit den einwandfreien Betrieb 

über die 4 unteren LEDs der AMS-Anzeige an
Alarmmeldung bei Überschreiten von Alarmgrenzen

Wird eine Alarmgrenze überschritten, wird dies über die blinkende Dreiecks-LED 

Anzeige (TAS) und die jeweilige Alarm LED angezeigt. Gleichzeitig löst (pulst) 

der interne Warnsummer der Auswerteeinheit und falls der Warnsummer in der 

Sensoreinheit mit der Auswerteeinheit verbunden ist, löst (pulst) auch dieser 

aus. Die entsprechenden Alarmrelais fallen ab. Die Dreiecks-LED, die Alarm 

LED und die Warnsummer gehen automatisch aus, wenn die Alarmgrenzen 

unterschritten werden.
Alarmmeldung bei Sensorstörung

Bei einer Sensorstörung blinken sowohl die Dreiecks-LED (TAS), die Alarm 1-, 

Alarm 2-, die Sensor LED und die Warnsummer werden aktiviert. Nachdem die 

Störung behoben ist, zeigen die LEDs den aktuellen Status wieder an.
Alarmquittierung

Sowohl mit dem Quittiertaster auf der rechten Seite des Gehäuses der Aus-

werteeinheit, als auch mit dem extern anschließbaren Quittiertaster können die 

Warnsummer zurückgesetzt werden. Nach dem Quittieren blinkt die Dreiecks-

LED (TAS) weiter und die LED Anzeige AMS ist permanent an. Sollte die 2. 

Alarmgrenze überschritten werden wird die Alarmmeldung, wie beschrieben, 

erneut ausgelöst und kann ebenfalls quittiert werden.
LED und Warnsummer Test

Sowohl mit dem Quittiertaster auf der rechten Seite des Gehäuses der Aus-

werteeinheit, als auch mit dem extern anschließbaren Quittiertaster kann eine 

Funktionsprüfung aller LEDs und der Warnsummer erfolgen.
-  Die rote Dreiecks-LED Anzeige (TAS) wird eingeschaltet

-   Die grüne LED Ausrufezeichen (AMS) wird eingeschaltet

-  Die Alarm 1-, Alarm 2- und Sensor LED wird eingeschaltet

-   Der interne Warnsummer wird eingeschaltet

-   und falls angeschlossen der externe Warnsummer wird eingeschaltet

Functions 

Sensor Connection

An external sensor with a 4-20mA output signal can be used.
Alarm Limits 

Alarm limits can be set by DIP-switches (see wiring diagram).
Display in normal operation

In normal operation, the EGS unit indicates proper operation by the 4 lower 

LEDs of the AMS display.
Alarm message when alarm limits are exceeded

If an alarm limit is exceeded, this is indicated by the flashing triangular LED 

display (TAS) and the respective alarm LED.

The internal warning buzzer of the evaluation unit is activated (pulsed) and 

also the buzzer in the sensor unit is activated (pulsed) if connected. 

The corresponding alarm relays are switched off. The triangle LED, the 

alarm LED and the warning buzzer are reset automatically when the gas 

concentration returns to normal conditions.
Alarm message in case of sensor fault 

In the event of a sensor fault, both the triangle LED (TAS), the alarm 1-, 

alarm 2-, the sensor LED and the warning buzzer are activated. After the fault 

has been rectified, the LEDs will indicated the current status again.
Alarm acknowledgment

The warning buzzers can be reset by either the internal acknowledgment button 

located on the right side of the evaluation unit or by an externally connected 

acknowledgment button. After acknowledgment, the triangle LED (TAS) con-

tinues flashing and the AMS LED indicator is permanently on. If the 2

nd

 alarm 

limit is exceeded, the alarm message is triggered again (similar to 1

st

 alarm) 

and can also be acknowledged.
LED and warning buzzer test

A function test of all LEDs and the warning buzzer can be activated by either 

the internal acknowledgement button of the evaluation unit or by an externally 

connected button.
-  The red triangular LED indicator (TAS) is switched on

-   The green LED exclamation mark (AMS) is switched on

-   The Alarm 1-, Alarm 2- and Sensor LEDs are switched on 

-   The internal buzzer is switched on

-   If connected, the external buzzer is switched on

Anschließbare Sensoren / 

Connectable Sensors

EGS CO2 SE

22V DC

Signal 4-20mA

Kurzbeschreibung 

Das Gaswarngerät EGS AE ist speziell 

zum Melden von Lecks in Kälteanlagen 

vorgesehen.  Mit  einem  speziellen 

externen Sensormodul können Lecks 

von  Kältemittel-  oder  CO2-Anlagen 

erfasst werden.

Wird  ein  Gas  detektiert,  dann  wird 

dies über einen großen, dreieckigen  

LED-Alarm, akustisch und über zwei 

Alarmrelais weitergemeldet. 

Zusätzlich  ist  es  möglich,  an  die 

Auswerteinheit (AE) einen Reset/Test-

Taster anzuschließen.

Die in der Sensoreinheit (SE) befind-

liche Hupe muss, zur Alarmierung, an 

die Auswerteeinheit (AE) angeschlos-

sen werden.

Mit Relais 1 kann z.B. eine Absaug-

vorichtung eingeschaltet werden, mit 

Relais 2 kann die Anlage abgeschaltet 

oder eine Störmeldung weitergeben 

werden. 

Nachdem  die  Konzentration  wieder 

gesunken ist, werden Relais und LED's 

zurückgesetzt. Der Signaleingang für 

das Sensorelement wird intern über-

wacht, liegen die Signale außerhalb 

des Bereichs, wird ein Fehler ange-

zeigt (LED "Sensor"). 

Brief Description 

The EGS AE utilizes a special external 

sensor  module  to  effectively  detect 

refrigerant  or  CO2  leaks  in  cooling 

facilities.

If a gas concentration above the 

defined limit is detected, a large 

triangular LED alarm is activated, along 

with an audible alarm and up to two 

alarm relays. 

This  allows  flexible  alarm  signaling 

and forwarding. 

After the gas concentration has 

dropped down to normal conditions,  

the relays and the LED's are reset. 

The signal input of the external gas 

sensor element is monitored 

internally. 

If the signal is out of range, LED 

'Sensor' indicates a failure.