Temperature 
Sensor connect 

+  -

 

 To Load 

 

L   E   N 

 Mains 

 

Diagnostic LED 

Fault LED 

 

C

OMMISSIONING

 

 

 

Mains Power Up 

1)

 

With no external connections made to the PSE, connect the mains input wires to the terminal block, 

ensuring that the mains isolator (disconnect device) is open

. Fasten wiring in place with cable tie to 

saddle. 

Note: Equipment must be earthed.

 

2)

 

Apply mains input. Confirm that all LED indicators flash on briefly proving integrity of indicating circuits. 
Ensure that the green Mains LED then stays illuminated and that the yellow Fault LED flashes after 
approximately 3 s (indicating a disconnected battery). 

3)

 

Disconnect the mains power. 

 
 

Load Output and Remote Signalling 

4)

 

Connect the EPS and GEN PSE Fault outputs to the appropriate inputs of control equipment if remote fault 
monitoring is required. 

5)

 

Loop the load (output) wiring through the supplied ferrite EMC suppressor. Cable tie to saddle provided 
(adjacent to exit hole).  

 

Figure 3 – Connections 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

6)

 

Re-apply mains. Verify that the green Mains LED illuminates and the yellow Fault LED flashes after 
approximately 3 s (disconnected battery). 

7)

 

If connected, verify that the EPS Fault monitor shows a 

closed

 contact and the GEN PSU Fault monitor 

shows an 

open

 contact. 

8)

 

Perform a full functional test of connected system (load) including full alarm condition

 
Figure 4 – Terminal labels 

 
 
 
 
 
 
 

 
 

   +    - |  +    -  |  GEN    EPS |Temp 
   Load|   Batt |     Fault       | 

BATT FUSE 
    5 Amp 

LOAD FUSE 
    5 Amp 

Summary of Contents for STX2405-E

Page 1: ...elay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting...

Page 2: ...Sonic model Yuasa model Interlogix model 2 x 2 1 Ah 12 V PS12021 NP2 1 12 2 x 7 Ah 12 V PS12070 NP7 12 2 x 17 18 Ah 12 V PS12170 NP17 12 BS131N Battery Charging Constant current bulk charging to 80 ca...

Page 3: ...le Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None No fault OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present...

Page 4: ...the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed from a mains...

Page 5: ...when loaded Ensure that wall fixings are appropriate to support this weight The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if i...

Page 6: ...ashes after approximately 3 s indicating a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and GEN PSE Fault outputs to the appropriate inputs of...

Page 7: ...tor shows a closed contact and the GEN PSU Fault monitor shows a closed contact 18 Disconnect one of the battery leads ensuring that no exposed section of conductor or connector is allowed to contact...

Page 8: ...an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal fa...

Reviews: