Technical Support: +44(0)23 9269 6638 (option 3) 

PAK200581_01N October 2015                        ©2015 ELMDENE INTERNATIONAL LTD  

WARNING: ALWAYS FIT 2 BATTERIES and wire in series, 
the product will NOT work with a single 12 V battery 

Fit 2 x 12V  
7 Ah batteries 

Mounting 
Points 

Fit 2 x 12V  
17/18 Ah batteries 

Mounting – C Box – 7 Ah 

5)

 

The C box is designed to support two 7 Ah batteries, and as such weighs a total of 9 Kg when loaded. 
Ensure that wall fixings are appropriate to support this weight.  
 

Mounting – E box – 17 or 18 Ah  

6)

 

The E box is designed to support two support two 17 or 18 Ah batteries, and as such weighs 18.5 Kg when 
loaded. Ensure that wall fixings are appropriate to support this weight. The product should be mounted no 
further than 10 cm from the control and indicating equipment, close coupled by conduit if it is being used 
to power the CIE directly.  

7)

 

Fix to wall or other structure in correct orientation i.e. with hinge on left hand side, using screws of 
sufficient size and length through the mounting holes. 

8)

 

Protect the battery terminals from any metal surfaces during installation as shorting of the terminals is 
hazardous. 

9)

 

Knock-outs are provided in the case for mating with external trunking or conduit. 

10)

 

Ensure that all unused holes (on the rear of the case) are sealed to prevent the ingress of damp and dust. 

 

Figure 1 – Box Mounting                 “E” Enclosure 

 

 

 

              “C” Enclosure 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 2 – Battery fitting and assembly 

Summary of Contents for STX2405-E

Page 1: ...elay fault output signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an optional plug in serial interface that can provide diagnostic and fault reporting...

Page 2: ...Sonic model Yuasa model Interlogix model 2 x 2 1 Ah 12 V PS12021 NP2 1 12 2 x 7 Ah 12 V PS12070 NP7 12 2 x 17 18 Ah 12 V PS12170 NP17 12 BS131N Battery Charging Constant current bulk charging to 80 ca...

Page 3: ...le Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None No fault OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present...

Page 4: ...the PSE is used as a power supply for Control and Indicating Equipment CIE the PSE shall be installed no further than 10cm from the CIE and close coupled by conduit This unit must be fed from a mains...

Page 5: ...when loaded Ensure that wall fixings are appropriate to support this weight The product should be mounted no further than 10 cm from the control and indicating equipment close coupled by conduit if i...

Page 6: ...ashes after approximately 3 s indicating a disconnected battery 3 Disconnect the mains power Load Output and Remote Signalling 4 Connect the EPS and GEN PSE Fault outputs to the appropriate inputs of...

Page 7: ...tor shows a closed contact and the GEN PSU Fault monitor shows a closed contact 18 Disconnect one of the battery leads ensuring that no exposed section of conductor or connector is allowed to contact...

Page 8: ...an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal fa...

Reviews: