Technical Support Line +44 (0)23 9269 6638 (Option 3) 

PAK200360 Iss 03B   Mar 2012 

©2012 ELMDENE INTERNATIONAL LTD 

 

C

OMMISSIONING

 

 

 
1)

 

Fit timer link to select 5s sound -off time. 

2)

 

Fit link to select SCB or SAB mode as required. 

3)

 

Connect ENG input to H+ or to a switched output of control panel set high. 

4)

 

Apply power to the sounder via H+ and H- from control panel. 

5)

 

Connect R-, ST- and TR to their respective outputs on the control panel. 

6)

 

Connect the black battery lead to BT- (slide sleeve to expose conductor). 

7)

 

Check tamper signal is present at control panel (circuit open). This verifies the ENG function. 

8)

 

Disconnect ENG input (or switch low from panel). 

Note: Sounder will operate

 

9)

 

Fit cover. Sounder will stop. This verifies the tamper operation. 

10)

 

Check tamper signal is removed at control panel (circuit closed). 

11)

 

Test sounder by triggering R- input. 

12)

 

Test strobe operation by triggering ST- input. 

13)

 

Remove cover. 

Note: Sounder will operate and a tamper will be signalled to the control panel.

 

14)

 

Remove timer link to select 15min sound -off time. 

15)

 

Re-fit cover and secure using fixing screws. 

16)

 

Disconnect H+ and check that the siren activates. Restore H+. 

17)

 

Disconnect H- and check that the siren activates. Restore H-. 

18)

 

Commissioning complete. 

 

M

AINTENANCE

 

 

 
The 

Quartz 

sounder should be tested for correct operation on a periodic basis. A minimum of one 

check every 12 months is recommended. The following features should be verified on each 
maintenance visit: 
1)

 

Correct operation of sounder and strobe from control panel signals 

2)

 

Correct operation of cover and rear tampers. 

3)

 

Remove the H+ supply from the control panel and check that the internal battery voltage as 
measured between BT+ and BT- is greater than 6.0v dc. If the battery voltage is less than this 
value replace the battery and re-connect observing CORRECT polarity. 

4)

 

Check for signs of significant water or insect ingress. Clean as necessary. 

 

SAB

 

B

ATTERY 

R

EMOVAL

 

 

 
The SAB battery may be removed for disposal at end of product life or if it is detected faulty when 
tested (see Maintenance above). To remove the battery, disconnect red and black leads from BT+ 
and BT- and unclip battery from holder. To fit a new battery, clip into holder, route battery cables 
around clips and reconnect positive (RED) lead to BT+ and negative (BLACK) lead to BT-. 
IMPORTANT: Ensure correct polarity of connections and that exposed battery leads DO NOT 
accidentally touch. 

 

 

Dispose of used batteries in accordance 

with all national and local regulations 

 

 

 

             

 

                

    6 

Summary of Contents for QUARTZ-1000-G2

Page 1: ...ounding Silent Engineer Start up Selectable sound auto cut off timer Selectable SAB or SCB operating mode Integral 1 Watt Xenon tube strobe Active inrush current limit on strobe Strobe Power Save Mode...

Page 2: ...he TS Tamper Source will normally be connected to the TR Tamper Return of the next sounder except for the last unit which will have TS linked to H See Fig 3 Engineer Mode This selects silent start up...

Page 3: ...ation or maintenance In engineer test mode apply a positive signal to prevent self activation of siren by tamper condition e g lid open H Permanent positive hold off supply H Permanent negative hold o...

Page 4: ...8 Option 3 PAK200360 Iss 03B Mar 2012 2012 ELMDENE INTERNATIONAL LTD Fig 2 Single Quartz Tamper Connection ENG H H TS TR R ST TAMP IN ST R H H TS ST TR R H H ENG CONTROL PANEL UNIT 1 UNIT 2 Fig 3 Mult...

Page 5: ...holes as required for fixing the backplate to the wall and for cable entry to the rear of the unit 3 Fit tamper extender if required and trim to desired length 4 Route cable from control panel throug...

Page 6: ...store H 17 Disconnect H and check that the siren activates Restore H 18 Commissioning complete MAINTENANCE The Quartz sounder should be tested for correct operation on a periodic basis A minimum of on...

Page 7: ...sounders on one tamper loop Cover or Rear tamper switch not closed Check cover and rear tamper switches fully closed DISPOSAL OF PRODUCT AT END OF LIFE This product falls within the scope of EU Direc...

Page 8: ...Ni MH Voltage 6 0V Capacity 320 mAH Strobe Rating 1 Watt Flash Rate 1 Hz reduces to 1 2 Hz after 15 minutes Comfort LEDs Alternate flash 60 per minute Material 3mm Polycarbonate all parts Tamper Detec...

Reviews: