Mechanical  

Model 

G2401BMU / G2402BMU 

G2403BMU / G2405BMU 

Module Dimensions  
w x h x d (mm / external)

 

152 x 106 x 52 

157 x 143 x 55 

Recommended Batteries 

2 x 12V NP7 or NP17 

Weight  (excluding batteries)

 

G2401BMU / G2402BMU 

G2403NU / G2405NU 

280g 

650g 

Environmental 

Temperature  

-10 to +40°C (operating) 95% RH non-condensing 
-20 to +80°C (storage) 

 

Connections  

+O/P 

+ve voltage O/P to load equipment   

-O/P 

-ve voltage O/P to load equipment   

+BATT 

Red lead to standby battery 1 

-BATT 

Black lead to standby battery 2 

GEN FAULT 

Volt-free contacts for general faults 

EPS FAULT 

Volt-free contacts for loss of mains indication 

 

 

O

PERATION

 

 

 
This unit is intended for use by Service Personnel only - There are NO USER SERVICEABLE parts inside. 
The Green Mains LED will be illuminated whilst the mains supply is present. In the event of a fault condition, 
the  Yellow  Fault  LED  will  be  illuminated.  The  Orange  Battery  Charging  LED  will  be  illuminated  when  the 
battery  is  not  fully  charged  and  is  charging  normally.  When  the  battery  is  fully  charged  it  will  be 
extinguished. 
 
 

I

NSTALLATION AND 

S

ET

-U

P

 

 

 
This unit is only suitable for installation as permanently connected equipment.  The PSU is

 

NOT SUITABLE 

for 

external  installation

.  EQUIPMENT  MUST  BE  EARTHED

.  Before  installation,  ensure  that  external  disconnect 

device  is

  OFF

.  The  PSU  should  be  installed  according  to  all  relevant  safety  regulations  applicable  to  the 

application.  
 

Module Enclosure & Mounting 

This  power  supply  module  has  high  voltage  present  and  is  for  use  by  Service  Personnel  only.  This  power 
supply  module  MUST  be  securely  mounted  within  a  robust  enclosure  having  suitable  means  to  prevent 
unintentional access to the module. Suitable notices must be affixed to the outside of the enclosure to warn 
of high voltages present internally. 

 
Mounting  

1)

 

Mount securely in correct orientation allowing minimum clearance of 20mm all round – see diagrams 
below.  

Summary of Contents for G240 BMU Series

Page 1: ...be used across a wide geographical area The highly efficient switch mode design ensures low operating costs while generating less heat The modular construction simplifies maintenance Universal mains...

Page 2: ...t circuit removed under mains power only Local Indicators MAINS LED Green FAULT LED Yellow Charge LED Orange Status ON OFF OFF NORMAL Battery fully charged ON OFF ON NORMAL Battery charging ON 1s ON 1...

Page 3: ...vent of a fault condition the Yellow Fault LED will be illuminated The Orange Battery Charging LED will be illuminated when the battery is not fully charged and is charging normally When the battery i...

Page 4: ...is is normal 9 Verify load is operating correctly 10 Disconnect mains power Signalling Outputs 11 Connect EPS and GEN fault outputs to appropriate inputs of control equipment Standby Battery 12 Connec...

Page 5: ...n 3 PAK200567_01B 2016 ELMDENE INTERNATIONAL LTD Module Dimensions 128 98 42 4 60 51 19 84 152 12 4 106 13 G2401BMU G2402BMU 157 1 2 8 7 5 128 42 4 1 9 6 0 5 6 5 4 1 3 5 1 4 3 12 G2403BMU G2405BMU Fix...

Page 6: ...eplacement of the battery If the output of the PSU fails the cause of the failure should be investigated e g short circuit load The fault should be rectified before restoring power to the PSU The fuse...

Page 7: ...7 Technical Support 44 0 23 9269 6638 option 3 PAK200567_01B 2016 ELMDENE INTERNATIONAL LTD This page has been intentionally left blank...

Page 8: ...Before disposal of the product the standby battery must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Pack...

Reviews: