M

AINTENANCE

   

 

There  is  no  regular  maintenance  required  of  the  PSU  other  than  periodic  testing  and  replacement  of  the 
standby batteries.  

Reference should be made to the battery manufacturer’s documentation to determine 

typical/expected battery life with a view to periodic replacement of the battery.   

If the output of the PSU fails the cause of the failure should be investigated e.g. short circuit load.  The fault 
should  be  rectified  before  restoring  power  to  the  PSU.    The  fuses  may  need  to  be  replaced.    Ensure  the 
correct fuse rating and type is used.  

Model Specification Table 

G2401BMU 

G2402BMU 

G2403BMU 

G2405BMU 

Output Current 

1A 

2A 

3A 

5A 

Max Mains Input Current (at 90Vac) 

1.0A 

1.3A 

1.4A 

2.0A 

F1 - Mains Input Fuse (20mm HRC) 

T2.0A 

T2.0A 

T3.15A 

T3.15A 

F2 - Output Fuse (20mm) 

F1.0A 

F2.0A 

F3.15A 

F5.0A 

F3 - Battery Fuse (20mm) 

F1.0A 

F2.0A 

F3.15A 

F5.0A 

Summary of Contents for G240 BMU Series

Page 1: ...be used across a wide geographical area The highly efficient switch mode design ensures low operating costs while generating less heat The modular construction simplifies maintenance Universal mains...

Page 2: ...t circuit removed under mains power only Local Indicators MAINS LED Green FAULT LED Yellow Charge LED Orange Status ON OFF OFF NORMAL Battery fully charged ON OFF ON NORMAL Battery charging ON 1s ON 1...

Page 3: ...vent of a fault condition the Yellow Fault LED will be illuminated The Orange Battery Charging LED will be illuminated when the battery is not fully charged and is charging normally When the battery i...

Page 4: ...is is normal 9 Verify load is operating correctly 10 Disconnect mains power Signalling Outputs 11 Connect EPS and GEN fault outputs to appropriate inputs of control equipment Standby Battery 12 Connec...

Page 5: ...n 3 PAK200567_01B 2016 ELMDENE INTERNATIONAL LTD Module Dimensions 128 98 42 4 60 51 19 84 152 12 4 106 13 G2401BMU G2402BMU 157 1 2 8 7 5 128 42 4 1 9 6 0 5 6 5 4 1 3 5 1 4 3 12 G2403BMU G2405BMU Fix...

Page 6: ...eplacement of the battery If the output of the PSU fails the cause of the failure should be investigated e g short circuit load The fault should be rectified before restoring power to the PSU The fuse...

Page 7: ...7 Technical Support 44 0 23 9269 6638 option 3 PAK200567_01B 2016 ELMDENE INTERNATIONAL LTD This page has been intentionally left blank...

Page 8: ...Before disposal of the product the standby battery must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Pack...

Reviews: