background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200415_01C May 2016                        ©2016 ELMDENE INTERNATIONAL LTD  

O

PERATING 

I

NSTRUCTIONS

 

 

 

In the event of loss of mains, a battery fault or a PSU fault, the corresponding Fault signal contacts will open. If the output of 
the PSU fails, the cause of the failure should be investigated e.g. short circuit load, connection of a deeply discharged 
battery. The fault should be rectified before restoring power to the PSU. If any of the fuses require replacing, ensure the 
correct fuse rating and type is used.  

 

P

REVENTATIVE 

M

AINTENANCE

 

 

 

This unit is intended for use by Service Personnel only.  There are NO USER SERVICEABLE parts inside. 
 
There is no regular maintenance required of the PSU other than periodic testing, calibration check  and replacement of the 
standby batteries.  

Reference should be made to the battery manufacturer's documentation to determine 

typical/expected battery life with a view to periodic replacement of the battery.  

 

C

ALIBRATION 

C

HECK

 

 

 

This power supply does not require calibration. If it is necessary to validate the calibration to comply with system inspection 
requirements then use the following procedure.  
1)

 

Set a calibrated DVM on maximum resolution range to read 6.00 Vdc. 

2)

 

Connect meter to calibration pins marked J4. 

3)

 

Verify that the meter reading is within the range 5.00 – 5.50 Vdc. 

If the unit fails its calibration check, it will continue to function but with reduced accuracy of detection of Low Battery 
voltage and Low output voltage. Please contact the manufacturer for recalibration options. 

 

S

INGLE 

B

ATTERY 

O

PERATION

 

 

 

The unit may be operated with only one battery. To avoid generating a fault condition cve (red) battery lead to 
Bat1+ and Bat2+, and connect the -ve (black) Battery lead to either Bat1- or Bat2-. 

 

CAUTION 

Dispose of used batteries according to the battery manufacturer’s 

instructions and all local and national regulations. 

 
 
 