Technical Support: +44(0)23 9269 6638 (option 3)
PAK200415_01C May 2016 ©2016 ELMDENE INTERNATIONAL LTD
S
PECIFICATION
(
CONT
.)
Load output fuse
F3.15A 20mm, 250Vac glass
Battery fuses (1 & 2)
2 x F3.15A 20mm, 250Vac glass
Ripple
<100mV pk – pk
@ 230Vac
<200mV pk – pk @ 230Vac -15%
Mechanical
Size (w x l x h)
170mm x 310mm x 80mm
Weight
2.8kg
Environmental
Temperature - operating
-10 to +40
O
C 75% RH non-condensing
Temperature - storage
-20 to +80
O
C
*
As calculated according to EN50131-6: 1997 Table 2.0 with maximum battery capacity fitted.
S
TAND
-B
Y
B
ATTERY
M
ANAGEMENT
Warning: risk of explosion if incorrect battery type fitted
Maximum Battery Size
2 x 17Ah 12V Valve Regulated Lead Acid (not supplied with unit)
Intelligent Battery Recharge Time
< 24 hours to 80%
A heavily discharged battery having a terminal voltage > 5.0V will attempt to be
charged. If battery fails to accept charge in 24 hours it will fail the active load test.
Testing
Battery Not Present: <5.5v battery voltage
Low battery voltage: <11.6v (no mains present)
Active load test at full rated output current
Protection
Reverse battery connection protection
Deep Discharge Protection
Both batteries disconnect when both have < 10.5v battery terminal voltage
Quiescent Current
100 mA when running on battery
< 100 μA after deep discharge protection.
S
IGNALLING
O
UTPUTS
Rating
0.10A @ 60vdc 16Ω solid state relay contacts, voltfree.
EPS Fault
Open if Loss of mains for >8s
APS Fault
Open if for
either
battery:
Battery terminal voltage < 11.6v (with mains off), or
Active Battery Monitoring detects a failed battery
PSU Fault
Open if Output voltage < 9.0v, or
Output short circuit, or
Output fuse blown
L
OCAL
D
IAGNOSTICS
Green LED
On = Mains Present
2 x Red LED’s (Bat1 & Bat2)
Individual battery Diagnostics according to table:
Green LED (mains)
Red LED (Bat1 & Bat2)
Status
ON
OFF
Normal
. Battery fully charged
ON
One short flash
Normal.
Battery charging
ON
Two short flashes
Fault.
Battery self test (load test) fail.
ON
Three short flashes
Fault.
No Battery or battery fuse failed)
ON
Both Flashing: 1 second on 1 second off
Fault.
No Output (Fuse blown or short circuit)
OFF
OFF
Fault.
No mains. No output. Batteries
disconnected or fully discharged
OFF
One short flash
Normal. Standby Mode.
Battery present,
healthy and supplying load.
OFF
Two short flashes
Fault.
Battery low voltage (<11.5v).