background image

Technical Support Line +44 (0)23 9269 6638         2402STE              PAK200480  Issue 01H May 2016             

Page 4 of 4 

 

Maintenance 

 

There is no regular maintenance required of the PSU as the microcontroller performs regular health checks of the battery and output voltage. 

However, reference should be made to the battery manufacturer’s documentation to determine typical / expected battery life with a 
view to periodic replacement of the battery.  

If the output of the PSU fails the cause of the failure should be investigated e.g. short circuit load, connection of a deeply discharged battery. The 
fault should be rectified before restoring power to the PSU. The following fuses may need to be replaced. Ensure the correct fuse rating and type 
is used. 
 
Load Output Fuse 

 

T2A 20mm, 250Vac glass 

Internal Mains Fuse   

T3.15A 20mm, 250Vac HBC 

Battery Fuse 

 

T2A 20mm, 250Vac glass 

CAUTION 

Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to 

the battery manufacturer’s instructions and all local and national regulations 

The packaging supplied with this product may be recycled. Please dispose of packaging accordingly. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Reviews: