Tamper 

20)

 

Connect tamper switch to appropriate inputs of control and indicating equipment (CIE). 

 
 

 
 

 

 

Fig 9  Position of tamper assembly on ‘clam shell’ style enclosures 

 

21)

 

Close the lid and fasten with screw supplied. Alternatively for ‘clam shell’ style fit the cover in place, 
the correct orientation is with the cover retaining feature engaging over the bottom lip of the base, 
fasten with screws supplied.  

22)

 

With the unit mounted on the wall check that the rear tamper is not in a position that will affect its 
operation, for example over a mortar course, recess or raised area on the wall. 
Check that the tamper switch is: 

CLOSED when the lid/cover is closed and the retaining screws are fitted, 
OPEN when the retaining screws are removed and the lid/cover is open. 

Use fine adjustment screw if necessary to align indicator with set point. 

23)

 

Close the lid/cover and fasten. 

24)

 

Re-check tamper circuit is closed at the control panel. 

 

O

PERATING 

I

NSTRUCTIONS

 

 

 
In the event of loss of mains, a battery fault or a GEN fault, the corresponding Fault signal contacts will open. 
 
If the output of the PSU fails, the cause of the failure should be investigated e.g. short circuit load, 
connection of a deeply discharged battery. The fault should be rectified before restoring power to the PSU. If 
any of the fuses require replacing, ensure the correct fuse rating and type is used.  

Lid Fixing Screw 

(Sets tamper switch) 

Tamper switch Connections 

Fine adjustment screw 

Set position indicator 

Summary of Contents for 20182423N

Page 1: ...tage dips do not create a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging or a fault condition Comprehensive protection...

Page 2: ...ng battery 4 0 Material 1 2mm steel white powder coated Environmental Temperature 10 to 40 C operating 75 RH non condensing 20 to 80 C storage Standby Battery Management Warning risk of explosion if i...

Page 3: ...FAULT Relay output for mains fail Open if loss of mains GEN FAULT Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity APS FAU...

Page 4: ...oad Output 8 Loop correctly rated load cable through supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green...

Page 5: ...n LED is ON 16 Disconnect battery Check that Red Fault LED is indicating a fault refer to diagnostic table on page 7 and that the control panel is showing an APS fault 17 Reconnect battery Check there...

Page 6: ...wall Check that the tamper switch is CLOSED when the lid cover is closed and the retaining screws are fitted OPEN when the retaining screws are removed and the lid cover is open Use fine adjustment s...

Page 7: ...N Normal Battery fully charged One short flash every second ON Normal Battery charging but not fully charged Flashing 1second On 1 second Off ON Fault Output fuse or battery fuse blown or battery PSU...