O

UTPUTS

 

 

 
Rating: 

0.10A @ 60Vdc 16Ω solid state relay contacts, volt free. 

EPS Fault:  

Open if Loss of mains for >10s 

GEN Fault: 

Open if Output voltage < 9.0V, or 

 

Output short circuit, or Output fuse blown 

APS Fault: 

Open if Battery terminal voltage < 11.6V, or 

 

Active Battery Monitoring detects a failed battery, battery fuse blown or 
battery not present. 

Tamper:  

0.5A @ 30Vdc volt free contact. Open when lid is open or 

 

unit removed from mounting surface.  

 

C

ONNECTIONS

   

 
O/P +, - 

Connection to equipment to be powered (Observe polarity) 

 

EPS (FAULT) 

Relay output for mains fail. Open if loss of mains. 

GEN (FAULT) 

Relay output for General Fault. Open in fault condition 

BATT +, - 

Connection to standby battery. Use cables provided (Observe polarity) 

APS (FAULT) 

Relay output for battery fail. Open if battery fail or low voltage 

 

I

NSTALLATION AND 

C

OMMISSIONING

 

 

 

This unit is only suitable for installation as permanently connected equipment.  This PSU is

 

NOT SUITABLE 

for 

external installation. 

 EQUIPMENT MUST BE EARTHED

. Before installation, ensure that external disconnect 

device is

 OFF

.

 

The PSU should be installed according to all relevant safety regulations applicable to the 

application.  

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig 1  Mounting of Power Supply 

L E N

 

Min 10cm clearance 

Fasten cables 
using cable tie 

 

 

3A min 

FUSED 
SPUR  

Load output cable: 
Current rating to 
match maximum load

 

Mains Input cable rated: 
3A, 300Vac minimum

 

Summary of Contents for 20182423N

Page 1: ...tage dips do not create a false loss of mains alarm Two LEDs assist with quick and easy installation by showing presence of mains correct battery charging or a fault condition Comprehensive protection...

Page 2: ...ng battery 4 0 Material 1 2mm steel white powder coated Environmental Temperature 10 to 40 C operating 75 RH non condensing 20 to 80 C storage Standby Battery Management Warning risk of explosion if i...

Page 3: ...FAULT Relay output for mains fail Open if loss of mains GEN FAULT Relay output for General Fault Open in fault condition BATT Connection to standby battery Use cables provided Observe polarity APS FAU...

Page 4: ...oad Output 8 Loop correctly rated load cable through supplied ferrite 1 turn and attach to terminal block note polarity Fasten with cable ties Fig 2 Position of ferrite 9 Apply mains power Check Green...

Page 5: ...n LED is ON 16 Disconnect battery Check that Red Fault LED is indicating a fault refer to diagnostic table on page 7 and that the control panel is showing an APS fault 17 Reconnect battery Check there...

Page 6: ...wall Check that the tamper switch is CLOSED when the lid cover is closed and the retaining screws are fitted OPEN when the retaining screws are removed and the lid cover is open Use fine adjustment s...

Page 7: ...N Normal Battery fully charged One short flash every second ON Normal Battery charging but not fully charged Flashing 1second On 1 second Off ON Fault Output fuse or battery fuse blown or battery PSU...

Page 8: ...al of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries...

Reviews: