HP602L-HP602LG
13
4 SIREN
PROGRAMMING
4.1 DEFAULT
PROGRAMMING
The siren can be programmed by either cutting or keeping a number of jumpers. The default settings are all closed.
The siren can be programmed in the following way:
•
Maximum siren time
= 3 minutes
•
Input reference
= positive
•
System status report
= disabled
4.2 SOUNDER TIME PROGRAMMING
This function is used to program the maximum delay after which the siren will automatically stop if the lock signal
persists (this function is useful is the wire was cut). The siren will generate a new alarm cycle the next time the lock
signal goes down.
JP3 CLOSED - JP4 CLOSED: SOUNDER TIME
= 3 min
JP3 CLOSED - JP4 OPEN:
SOUNDER TIME
= 6 min
JP3 OPEN - JP4 CLOSED:
SOUNDER TIME
= 9 min
JP3 OPEN - JP4 OPEN:
SOUNDER TIME
= 30 min
4.3 BL1 AND TC1 INPUTS REFERENCE
This function is used to program the BL1 and TC1 input references to either positive or negative.
JP5 CLOSED: POSITIVE REFERENCE
JP5 OPEN: FUNCTION ENABLED
4.4 SYSTEM STATUS REPORT
Should this function be enabled, TC signal absence will cause continuous flash blinking.
NOTE: when this function is enabled, alarm memory function won’t be available.
JP1 CLOSED: FUNCTION DISABLED
JP1 OPEN: FUNCTION ENABLED